OVP1 24VAC/DC TELE, OVP1 24VAC/DC Datasheet

RELAY, VOLTAGE PRESET, 0-10VDC

OVP1 24VAC/DC

Manufacturer Part Number
OVP1 24VAC/DC
Description
RELAY, VOLTAGE PRESET, 0-10VDC
Manufacturer
TELE
Datasheet

Specifications of OVP1 24VAC/DC

Relay Type
Coupling
Coil Voltage Vac Nom
28V
Coil Voltage Vdc Nom
28V
Contact Current Max
2A
Contact Voltage Ac Nom
28V
Contact Voltage Dc Nom
28V
Coil Type
AC/DC Coil
Nom Operating Power
330mW
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Coupling relays - OCTO series
1. Functions
AUTO
0
HAND
2. Indicators
Yellow LED ON/OFF:
3. Mechanical design
Self-extinguishing plastic housing, IP rating IP40
Mounted on DIN-Rail TS 35 according to EN 50022
Mounting position:
Shockproof terminal connection according to VBG 4
(PZ1 required), IP rating IP20
Initial torque:
Terminal capacity:
4. Input circuit
Supply voltage:
Tolerance:
Rated frequency:
Rated consumption:
Duration of operation:
Reset time:
Residual ripple for DC:
Drop-out voltage:
5. Output circuit
Output signal (terminals Y-GND):
Output capacity Y:
Insulation voltage:
Surge voltage:
Installation design
Width 17.5mm
Analog data encoder 0 to 10VDC
Checkback signal of the switch setting ‚AUTO‘
Technical data
Release 11/02
1 x 0.5 to 2.5mm² with/without multicore cable end
1 x 4mm² without multicore cable end
2 x 0.5 to 1.5mm² with/without multicore cable end
2 x 2.5mm² flexible without multicore cable end
Switch setting AUTO
Switch setting 0
Switch setting HAND
output according to input YR
permanently OFF
output according to set value (regulator)
intensity according to the value of the
output signal
any
max. 1Nm
24V AC/DC
24V AC/DC
48 to 63Hz
24V AC/DC
100%
-
10%
>30% of supply voltage
corresponding to input signal at
terminals YR - GND
0V
0 to 10V
10mW at 10V
(switch setting HAND)
24V AC (according to IEC 664-1)
800V, overvoltage category III
(according to IEC 664-1)
terminals A1(+)-A2
-15% to +10%
0.58VA (0.33W)
6. Checkback
Setting ‚AUTO‘:
Maximum switching capacity: 56VA (2A / 28V AC/DC)
Minimum switching capacity: 5mVA (1mA / 5V AC/DC)
Contact resistance:
Electrical life:
7. Accuracy
Base accuracy:
Adjustment accuracy:
Repetition accuracy:
Voltage inuence:
Temperature inuence:
8. Ambient conditions
Ambient temperature:
Storage temperature:
Transport temperature:
Relative humidity:
Pollution degree:
terminals B1-B2
max. 20mΩ
3 x 10
±1% (of maximum scale value)
±10% (of maximum scale value)
-
-
≤0.01% / °C
-25 to +55°C (according to IEC 68-1)
-25 to +70°C
-25 to +70°C
15% to 85%
(according to IEC 721-3-3 class 3K3)
2, if built-in 3
(according to IEC 664-1)
4
operations at maximum load
OVP1
4.02-4

Related parts for OVP1 24VAC/DC

OVP1 24VAC/DC Summary of contents

Page 1

... Coupling relays - OCTO series Installation design Width 17.5mm Analog data encoder 0 to 10VDC Checkback signal of the switch setting ‚AUTO‘ Technical data 1. Functions AUTO output according to input YR 0 permanently OFF HAND output according to set value (regulator) 2. Indicators Yellow LED ON/OFF: intensity according to the value of the output signal 3 ...

Page 2

... The input signal applied to terminal YR is looped through unchanged to terminal Y. Permanently OFF (0) The contact of checkback B1-B2 is opened. No output signal at terminal Y. Manual signal (HAND) The contact of checkback B1-B2 is opened. Output signal at terminal 10V DC) according to the value set on the front mounted regulator. Connections Dimensions www.tele-power-net.com ...