Specifications of TA8-A 100-230AC

Contact Configuration
DPDT
Nom Input Voltage
230VAC
Delay Time Range
0.05s To 60h
Adjustment Type
Knob
Relay Mounting
Plug-In
Svhc
No SVHC (15-Dec-2010)
Coil Voltage Vac Nom
230V
Contact Current
RoHS Compliant
TA8-A/TA8-SA/03/03
Electronic On-Delay Timers
TA8-A/TA8-SA
New short body on-delay timers, with 16 ranges
selectable from front panel. Plug-in or panel mounting
Options and ordering codes
Specification
Timing ranges (selectable)
Calibrated range – selected
using screw in bottom left
corner of front panel
0–6
0–12
0–30
0–60
Repeat accuracy
Reset time
Max. switching frequency
Allowable ambient temperature
Mechanical life
Electrical life
Allowable operating voltage range
Contact ratings
Power consumption
Supply frequency AC types
Dielectric strength
Insulation Resistance
Vibration
Shock
Timed contacts
Timing ranges 0.05 secs to 60 hours
16 ranges, front panel selectable
DPCO timed contacts or SPCO timed plus SPCO
instantaneous contact versions
New scale ranges for ease of time setting
Instantaneous output with dial set at 0
Improved resistance to electromagnetic interference
Indicators for time range, time up and power
on/timing
48-DIN
Plug-in octal base
Sockets available for panel, surface or DIN rail
mounting
Approved by standards: UL and CSA
DPCO
24VAC/DC
100-240VAC
48-127VDC
Controlled timing range. Time unit selectable using the screw in the bottom right hand corner of the front panel
Time unit: 0.1 sec.
0.05–0.6 secs.
0.1–1.2
0.25–3
0.5–6
TA8-A
voltage
instantaneous contacts
Timed contacts plus
±0.3% at max. setting time
0.1 sec or less
1800 times/hour
-10˚C to +55˚C (Avoid ice on timer)
20 million operations or more
100,000 operations or more at 250 V AC 5A resistive load
0.85 to 1.1 times input voltage (0.9 to 1.1 at 55˚C)
5A at 250 V AC resistive load
10VA at AC, 1W at DC
50/60 Hz
2,000 V AC rms. 1 min. between current carrying part and non current carrying part
2,000 V AC rms. 1 min. between output contacts and control circuit
1,000 V AC rms. 1 min. between open contacts
100 M or more at 500 V DC megger
Mechanical durability: 10 to 55Hz, 0.75mm double amplitude
Malfunction durability: 10 to 55Hz, 0.5mm double amplitude
Mechanical durability: 500m/s
Malfunction durability: 100m/s
SPCO
Time unit: sec.
0.5–6 secs.
1–12
2.5–30
5–60
24VAC/DC
100-240VAC
48-127VDC
2
2
(Approx. 50G)
(Approx. 10G)
TA8-SA
voltage
Time unit: min.
0.5–6 mins.
1–12
2.5–30
5–60
Time unit: hrs.
0.5–6 hrs.
1–12
2.5–30
5–60
www.imopc.com

Related parts for TA8-A 100-230AC

TA8-A 100-230AC Summary of contents

Page 1

... Electrical life Allowable operating voltage range Contact ratings Power consumption Supply frequency AC types Dielectric strength Insulation Resistance Vibration Shock TA8-A/TA8-SA/03/03 SPCO TA8-SA 24VAC/DC Timed contacts plus 100-240VAC voltage instantaneous contacts 48-127VDC Time unit: sec. 0.5–6 secs. 1–12 2.5–30 5–60 ± ...

Page 2

... Inst. NO 1-3 Inst. NC 1-4 LED POWER LED OUTPUT TA8-DA Power 2-7 Timed NO 1-3 8-6 Timed NC 1-4 8-5 TA8-TA Power 2-7 Timed NO 1-3 8-6 Timed NC 1-4 8-5 LED POWER LED OUTPUT Dimensions (mm) Net weight : Approx. 100g Sockets Surface/track mounting – screw terminal Net weight : Approx ...

Related keywords