D6F-P0010A2 Omron, D6F-P0010A2 Datasheet - Page 4

SENSOR AIRFLOW 0-50KPA W/CONN

D6F-P0010A2

Manufacturer Part Number
D6F-P0010A2
Description
SENSOR AIRFLOW 0-50KPA W/CONN
Manufacturer
Omron
Series
D6Fr
Type
MEMS Flow Sensorr
Datasheets

Specifications of D6F-P0010A2

Supply Voltage
5 VDC to 10 VDC
Sensing Range
0 ~ 1 LPM
Flow Sensor Type
Air
Voltage - Input
4.75 V ~ 9.45 V
Material - Body
PBT Plastic
Sensor Type
MEMS Flow Sensor
Rated Range
1 L/min
Analog Output
0 V to 3.1 V
Pressure Max
7psi
Supply Voltage Range Dc
4.75V To 5.25V
Accuracy
± 5%
Sensing Accuracy
5%
Output Voltage Max
2.5V
Flow Rate Min
0l/min
No. Of Ports
2
Sensor Terminals
Cable With Connector
Function
AirFlow
Output
Voltage
Primary Type
AirFlow
Range, Measurement
1 Liter/Min.
Technology
MEMS
Termination
Connector
Voltage, Supply
10 VDC
Voltage, Switching
4 VDC
Flow Rate Max
1l/min
Rohs Compliant
Yes
Accuracy %
5%
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Port Size
-
Switch Function/rating
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
D6FP0010A2
Z2786
Packaging
Application Information and Examples
■ Bidirectional Dust Segregation System
The D6F-P series has a patented dust segregation design. The flow path incorporates dual centrifugal chambers, in which particulate matter follows
in the outer path, away from the MEMS sensor chip regardless of the flow direction. Note, standard products are calibrated for unidirectional flow,
as indicated in note 3 of the “Output Characteristics” table, above. Contact Omron for bidirectional calibration options.
Bypass Setup
When used in a bypass set-up, as illustrated below, the D6F-P mass
flow sensors can measure flow rates far beyond the 1 LPM in-line rat-
ing. The pressure differential required to pull airflow through the sen-
sor can be accomplished by installing a flow restrictor between the
two ports or through the use of a flow cross in large ducts, as shown
in the HVAC application.
Note: Be sure to read the precautions and information common to all D6F sensors, contained in the Technical User’s Guide, “D6F Technical Information”
10
2
for correct use.
TYPE D6F-P
MEMS Mass Flow Sensor
1
sensing element
Display seal
D6F-P
3
HVAC Application
The D6F-P mass flow sensor is ideal for damper control in variable
air volume systems, where low flow rates are difficult to measure with
differential pressure sensors.
No.
1
2
3
Box (100 pcs)
Tray (25pcs)
Sock liner
Item
Polyethylene
Material
CCNB
CCNB

Related parts for D6F-P0010A2