CA2KN40U7 TELEMECANIQUE, CA2KN40U7 Datasheet

RELAY, CONTROL, 4N/O, 240VAC

CA2KN40U7

Manufacturer Part Number
CA2KN40U7
Description
RELAY, CONTROL, 4N/O, 240VAC
Manufacturer
TELEMECANIQUE
Datasheet

Specifications of CA2KN40U7

Relay Type
Control
Coil Voltage Vac Nom
240V
Contact Current Max
10A
Contact Voltage Ac Nom
690V
Coil Type
AC
Nom Operating Power
30VA
Relay Mounting
DIN Rail / Panel
External Width
45mm
Product data sheet
Characteristics
Complementary
Mon Oct 11 10:43:03 EDT 2010
Contact operation
Control circuit voltage limits
[Ui] rated insulation voltage
Flame retardance
Tightening torque
[Ue] rated operational voltage
[Ith] conventional free air thermal current
Irms rated making capacity
Associated fuse rating
Inrush power in VA
Hold-in power consumption in VA
Mechanical durability
Operating rate
Operating time
Minimum switching current
Minimum switching voltage
CA2KN40U7
contactor TeSys CA2-K - 4 NO - instantaneous
- 10 A - 230...240 V AC
Main
Range of product
Product or component
type
Device short name
Contactor application
Utilisation category
Control circuit type
Coil type
Coil technology
Pole contact composi-
tion
[Uc] control circuit volt-
age
Connections - terminals
Mechanically linked conforming to IEC 60947-5-1
0.8...1.15 Uc at 50 °C operational 50/60 Hz
<= 0.2 Uc at 50 °C drop-out 50/60 Hz
600 V - conforming to CSA C22-2 No 14
690 V - conforming to BS 5424
690 V - conforming to IEC 60947
750 V - conforming to VDE 0110 group C
V1 conforming to UL 94
Class C2 conforming to NF F 16-101
Class C2 conforming to NF F 16-102
0.8...1.3 N.m - on screwclamp terminal - with screwdriver Philips 2 mm
0.8...1.3 N.m - on screwclamp terminal - with screwdriver flat Ø 6 mm
<= 690 V AC <= 400 Hz
10 A at ≤ 50 °C
110 A at <= 690 V AC conforming to IEC 60947
10 A gG at <= 690 V conforming to VDE 0660
10 A gG at <= 690 V conforming to IEC 60947
30 VA at 20 °C
4.5 VA at 20 °C
10000000 cycles
10000 cyc/h at 20 °C
5...15 ms coil energisation and NC opening
10...20 ms coil energisation and NO closing
10...20 ms coil de-energisation and NO opening
15...25 ms coil de-energisation and NC closing
5 mA
17 V
TeSys k control relay
Electromagnetic relay
CA2K
Control circuit
AC-15
AC
Standard
Without integral suppression device
4 NO
230/240 V AC 50/60 Hz
Screwclamp terminal 1 cable 1.5 mm² - cable stiff-
ness: solid
Screwclamp terminal 2 cable 4 mm² - cable stiff-
ness: solid
Screwclamp terminal 1 cable 0.75 mm² - cable stiff-
ness: flexible - without cable end
Screwclamp terminal 2 cable 4 mm² - cable stiff-
ness: flexible - without cable end
Screwclamp terminal 1 cable 0.34...1.5 mm² - cable
stiffness: flexible - with cable end
Screwclamp terminal 1 cable 0.34...2.5 mm² - cable
stiffness: flexible - with cable end
1

Related parts for CA2KN40U7

CA2KN40U7 Summary of contents

Page 1

... Inrush power in VA Hold-in power consumption in VA Mechanical durability Operating rate Operating time Minimum switching current Minimum switching voltage Mon Oct 11 10:43:03 EDT 2010 CA2KN40U7 contactor TeSys CA2 instantaneous - 230...240 V AC Main Range of product TeSys k control relay Product or component Electromagnetic relay ...

Page 2

Non-overlap time Non overlap distance Insulation resistance Height Width Depth Product weight Environment Standards Product certifications IP degree of protection Protective treatment Ambient air temperature for operation Ambient air temperature for storage Operating altitude Shock resistance Vibration resistance Heat dissipation ...