KFD2-CD-EX1.32 PEPPERL & FUCHS, KFD2-CD-EX1.32 Datasheet

CURRENT DRIVER

KFD2-CD-EX1.32

Manufacturer Part Number
KFD2-CD-EX1.32
Description
CURRENT DRIVER
Manufacturer
PEPPERL & FUCHS
Datasheet

Specifications of KFD2-CD-EX1.32

Input Type
Intrinsically Safe
Output Type
4-20mA
Accuracy
± 0.1%
Supply Voltage Range
20V DC To 35V DC
Approval Bodies
BASEEFA
Input Voltage Max
35V
Input Voltage Min
20V
Isolation Input
Isolated
KFD2-CD-Ex1.32.*
1
Model.Number.
KFD-CD-Ex1..*
•. 1-channel.
•. .VDC.supply/Power.Rail.compatible.
•. Conversion.of.current/voltage.or..
•. Conversion.ranges:.0/-0.mA,.0/1-.V,.
•. Suitable.for.Division./Zone..mounting.
•. SIL..according.to.IEC.10;.SIL..in.a.
The KFD2-CD-Ex1.32.* series of analog current/voltage
drivers drive I/P converters, electrical valves and positioners
in hazardous areas. They are available in several designs.
INPUT/OUTPUT SELECTION TABLE
Match the desired inputs and outputs on this chart, then
use that number when ordering. The values shown in
parentheses are subsets of a larger range.
0-20mA
4-20mA
0-10V
2-10V
INPUT
0-5V
1-5V
Front View
Housing type A4
(see system description)
1-Channel
Current/Voltage
Driver
voltage/current.
0/-10.V.
redundant.structure
0-20mA 4-20mA 0-5V 1-5 V 0-10 V 2-10V
USA Headquarters
phone: 330 486-0002 • email: sales@us.pepperl-fuchs.com
0
1
3
-
6
-
Engineer's Guide (page 7)
Accessories (page 443)
Power Supplies (page 401)
Surge Suppression (page 413)
Lastest Info. Avail. Online
(0)
(3)
(6)
2
5
8
web: www.am.pepperl-fuchs.com
OUTPUT
(15)
21
-
-
-
-
(15)
-
-
-
-
-
Removable terminal
blue
Removable terminals
green
LED green:
Power supply
12
13
15
-
-
-
(12)
(15)
1
-
-
-
Worldwide Headquarters
phone: +49 621 776-0 • email: pa-info@de.pepperl-fuchs.com
Connection.Diagram
Technical Data
POWER.SUPPLY.
INPUT.(not.intrinsically.safe).
OUTPUT.(intrinsically.safe).
TRANSFER.CHARACTERISTICS.
CERTIFICATES.
MECHANICAL.
AMBIENT.TEMPERATURE
Nominal voltage
Rated current
Transmission range
Limitation, max. input
Voltage drop (current version)
Input current (voltage version)
Transmission range
Limitation, max. output
Resistance
Calibrated accuracy
Temperature drift
Rise time
Housing
Dimensions
Weight
Class I; Div 1, 2
Zone 0, 1, 2
Hazardous
Area
web: www.pepperl-fuchs.com
Current or
Voltage
(+) 1
(–) 2
Safe Area, Div 2 or Zone 2
Zone 0, 1, 2
Zone 2
Exida
KFD2-CD-Ex1.32
Power Rail Connection
≤ 0.1 % incl. non-linearity and hysteresis at 20°C
BAS 02 ATEX 7203,
TÜV 99 ATEX 1499 X,
4.21" x 0.79" x 4.53" (107 x 20 x 115 mm)
850 Ω max. load (current output version)
3 Ω max. load (voltage output version)
Asia Pacific Headquarters
phone: +65 67799091 • email: sales@sg.pepperl-fuchs.com
See page 184 for entity parameters
≤ 50 mA (current output version)
≤ 20 mA (voltage output version)
0-20 mA (current output version)
0-20 mA (current output version)
-4°F to +140°F (-20°C to +60°C)
0-10 V (voltage output version)
0-10 V (voltage output version)
Power Rail or terminals 7+, 8-
≤ 100 µA up to 50 °C at 10 V
Type A4 see page 454
Terminals 9+, 10-, 11+
17 V at 20 mA, 10 V
P+F 03/10-12 R014
≤ 40 mA, 12 VDC
Terminals 1+, 2-
3.5 oz. (≈ 100 g)
≈ 4 V at 20 mA
No. 116-0129
No. 116-0132
No. 116-0173
≤ 0.01 %/ºC
20-35 VDC
11 (+)
9 (+)
10 (–)
7 (+)
8 (–)
< 10 ms
24VDC
II (1) G D [EEx ia] IIC
web: www.pepperl-fuchs.com
V/I
II 3 G EEx nA II T4
I/O
Current or
Voltage
Source

Related parts for KFD2-CD-EX1.32