Specifications of C396B2A110SELXF

Overload Adjustment Current Min
22A
Overload Adjustment Current Max
110A
Frame Size
Standard
Contact Configuration
1NO / 1NC
March 2009
Contents
Description
Overload Relays — C396
Catalog Number
Product Selection . . . . . . . . . . 34-114
Accessories . . . . . . . . . . . . . . . 34-115
Technical Data and
Dimensions . . . . . . . . . . . . . . . 34-117
Reference Data . . . . . . . . . . . . 34-210
Catalog Number Selection
Table 34-137. C396 Electronic Overload Relays — Catalog Numbering System
CA08102001E
Selection . . . . . . . . . . . . . . . . 34-113
Specifications . . . . . . . . . . . . 34-116
C396 = C396 Electronic Overload Relay
C396 Electronic
Overload Relay
Device Type
2 = Standard
Feature Set
A = 45 mm
B = 65 mm
C = 110 mm
Frame Size
Page
A = Auto
Reset Type
C 3 9 6 A 2 A P 0 5 S E L A X
Product Description
The C396 is a self-powered, robust
electronic overload designed for inte-
grated use with Freedom NEMA,
IEC, and DP contactors. The overload
can be ordered as a stand-alone
version that is designed for Panel-
Mounting and for use on 35 mm DIN
rail. The C396 has an FLA range of
0.1 – 150 Amps with internal CTs, and
up to 1500 Amps using external CTs.
Features
For more information visit: www.eaton.com
Standard Version: Selectable trip
class (5, 10, 20, 30) with Selectable
Manual or Auto Reset
Broad 5:1 FLA range
Self-Powered Design, will accept AC
voltages from 12 – 690V 50/60 Hz
Ambient Temperature
Compensation
Low Heat Generation
Phase Loss Protection
Phase Unbalance Protection
Electrically isolated 1NO-1NC
Contacts (Push-to-Test)
Trip Status Indicator
FLA range of 0.1 – 1500 Amps
IEC Contactors & Starters
XT IEC Power Control
Overload Relays — C396
Frame A (45 mm)
P05 = 0.1 – 0.5
002 = 0.4 – 2.0
005 = 1 – 5
008 = 1.6 – 8
032 = 6.4 – 32
045 = 9 – 45
Frame B (65 mm)
075 = 15 – 75
110 = 22 – 110
Frame C (110 mm)
150 = 30 – 150
Max. Amperes
Current Rating
AX = All Frame Sizes
Frame B
Frame C
SEL = Selectable
XB = 0.1 – 0.5A
XC = 0.1 – 0.5A
Standards and Certifications
0.4 – 2.0A
1 – 5A
1.6 – 8A
6.4 – 32A
0.4 – 2.0A
1 – 5A
1.6 – 8A
6.4 – 32A
Stand-Alone Overload Relay Suffix
UL Listed Components: Stand-
alone, starter-mounted devices and
remote reset kit.
CSA Certified Components: Stand-
alone, starter-mounted devices and
remote reset kit.
IEC EN 60947-4-1, EN 60947-5-1
CE
RoHS
Class
XT IEC Adapter Suffix
Frame D
Frame F – G
XD =
XF = 22 – 110A
15 – 75A
6.4 – 32A
9 – 45A
34-113
34