I/O Connections
4-2
Terminal Block
I/O Connections
Note Putting I/O Lines and high-tension lines or power lines in the same duct or con-
Note When a Triac Output Unit is used to drive a low-current load, the load may not
Connect the I/O Devices to the I/O Units using AWG (cross-sectional area:
0.3 mm
tional area: 0.3 to 0.75 mm
screws with 3.5-mm diameter heads and self-raising pressure plates. Connect
the lead wires to the terminals as shown. Tighten the screws to a torque of 0.8
NSm.
Use ring crimp terminals for wiring. Do not connect bare stranded wires directly
to terminal blocks.
The terminal block of an I/O Unit can be removed by loosening the mounting
screws. You do not have to remove the lead wires from the terminal block in or-
der to remove it from an I/O Unit.
duit may cause the I/O Lines to be affected by noise. This may cause a malfunc-
tion in the I/O Unit or may cause damage to the I/O Unit or I/O devices.
turn completely OFF due to a leakage current. To compensate for the leakage
current, connect a bleeder resistor in parallel with the load.
7 mm max.
2
) for 19-terminal terminal blocks and AWG 22 to lead wire (cross-sec-
Terminal block mounting screws
Loosen the terminal block mounting screws to remove
the terminal block from the I/O Unit. Make sure the
mounting screws on the terminal block are tightened af-
ter wiring is complete, and the terminal block is re-
mounted to the I/O Unit.
2
) for 10-terminal terminal blocks. The terminals have
7 mm max.
Section 4-2
43