C500RM201 Omron, C500RM201 Datasheet - Page 62

no-image

C500RM201

Manufacturer Part Number
C500RM201
Description
WRITE MASTER
Manufacturer
Omron
Datasheet

Specifications of C500RM201

Leaded Process Compatible
No
Peak Reflow Compatible (260 C)
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Masters and Slaves
Terminator Selector
DIP Switch
52
Indicators
C200H Slave Switches
not lit
flash
---
---
flash
flash
flash
XMT/RCV
not lit
not lit
lit
lit
flash
lit
lit
ERROR1
not lit
not lit
---
lit
lit
lit
flash
ERROR2
C200H Slaves indicators function together to show the status of the System.
The RUN indicator is controlled by the mode setting on the CPU Unit.
The DIP switch and terminator selectors are accessed by removing the
switch cover on the front of the Slave. Use a regular screwdriver to open the
cover if necessary. Always be sure that the PC and Slave power are turned
off before setting the switches.
not lit
---
not lit
not lit
---
not lit
---
RUN
Terminator Setting
System not started or pow-
er off.
Normal transmission
Transmission error
I/O bus error
I/O verification error
I/O setting error
Expansion I/O Rack miss-
ing.
Status
Terminator
(Termination resistance ON)
Not terminator
(Termination resistance OFF)
Master is still testing System or power off.
Power has not yet been turned on.
Normal transmissions are occurring be-
tween Slave and Master.
Error has occurred in transmissions with
Master.
Error has occurred in I/O bus connecting
Slaves to I/O Units.
An I/O Unit configuration of Slave Rack
has changed.
An I/O Unit designation on the Slave Rack
is wrong.
An Expansion I/O Rack connected to the
Slave Rack with I/O Connecting Cable
cannot be confirmed by the PC.
Meaning
Section 4-1

Related parts for C500RM201