DTC41002240VAC TEMPATRON, DTC41002240VAC Datasheet

TEMPERATURE CONTROLLER, PT100

DTC41002240VAC

Manufacturer Part Number
DTC41002240VAC
Description
TEMPERATURE CONTROLLER, PT100
Manufacturer
TEMPATRON
Datasheet

Specifications of DTC41002240VAC

Thermocouple Type
PT100
Operating Temperature Max
50°C
Operating Temperature Min
0°C
Output Voltage Max
240VAC
Accuracy
± 2°C
Alarm Output Rating
500mA @ 120V Ac
Approval Bodies
CE
Tempatron Ltd, Darwin Close, Reading, Berks, RG2 0TB, UK Tel : 0118 931 4062 Fax : 0118 931 0175 e-mail : sales@tempatron.co.uk
The DTC410 range of on/off temperature
controllers are designed to offer the programmable
functionality of modern PID controllers but at a
price suited to on/off applications. The clear LCD
display and 2-button programming gives an easy to
use set-up procedure. Message displays also
provide a clear indication of alarms or error status.
Supply voltage: 24Vac/dc @ 60mA max.
Sensor options: J, K, T, N T/couples, PT100, 4-20mA
Scale ranges:
Gain accuracy:
Offset accuracy: T/c = +/- 5 C, PT100 = +/- 2 C
Outputs:
Approvals:
Ambient range:
Memory back-up: Lithium battery with 10 years
Weight:
SPECIFICATION
DTC410 ON/OFF TEMPERATURE CONTROLLER
4 programmable thermocouple inputs
PT100 & 4-20mA inputs
10 programmable alarm options
Direct or reverse action
Programmable set-point limits
110Vac, 50/60 Hz @ 1.5VA max.
220-240Vac, 50/60 Hz @ 1.5VA max
J T/c
T T/c
K/N T/c = -99 to 999 C or F
PT100 = -99 to 400 C (700 F)
4-20mA = scalable -99 to 999 units
T/c
Others = +/- 0.6% of scale range
Control: 3A @ 240Vac, SPCO relay
Alarm:0.5A @ 120Vac, SPNO relay
Conforms to CE generic standards
EN50081-1 and EN50082-1 for emc
and EN61010-1 for low voltage
-10 to 50 C non-condensing
operating life
205gms
DIGITAL TEMPERATURE CONTROLLERS
= +/- 0.25% of scale range
o
= -99 to 700 C (999 F)
= -99 to 300 C (570 F)
o
o
o
o
o
o
o
o
o
CONNECTION DIAGRAM
STANDARD ITEMS
DIMENSIONS
For details of suitable input sensors or our matching
UDT series timer please contact our sales office.
Alarm
Input
Thermocouple
PT100
4-20 mA
Wiring socket - panel mount
Wiring socket - DIN rail mount
SET
N
L
48 sq
24V
4
+
3
Thermocouple
Note : When pin 11 and the sensor
are both earthed, the DTC410 will
display OPN and will not operate
correctly. For 24V models use an
isolated or non-earthed sensor.
5
2
0V
input
6
1
Panel cut-out 45 x 45 mm
5
7
11
-
Voltage
24Vac/dc
110Vac
230Vac
24Vac/dc
110Vac
230Vac
24Vac/dc
110Vac
230Vac
Input
8
10
9
Control
70.5
5
5
sensor
-0
+0.5
4-20 mA
6
DTC410-01-24
DTC410-01-110
DTC410-01-230
DTC410-02-24
DTC410-02-110
DTC410-02-230
DTC410-03-24
DTC410-03-110
DTC410-03-230
RTD
input
input
Part Number
6
7
AZ511
AZ611
7
4-20mA
14
+
-

Related parts for DTC41002240VAC

Related keywords