TC4810-52 TEMPATRON, TC4810-52 Datasheet - Page 12

TEMPERATURE CONTROLLER, PT100

TC4810-52

Manufacturer Part Number
TC4810-52
Description
TEMPERATURE CONTROLLER, PT100
Manufacturer
TEMPATRON
Datasheet

Specifications of TC4810-52

Thermocouple Type
PT100
Operating Temperature Max
50°C
Operating Temperature Min
-10°C
Output Voltage Max
240VAC
Accuracy
± 2%
Approval Bodies
CE, EN50081-1, EN50082-1, EN61010-1
For suitable input sensors see page 26.
DIMENSIONS
CONNECTION DIAGRAM
STANDARD ITEMS
Voltage
100-240Vac
100-240Vac
100-240Vac
24Vac/dc
24Vac/dc
Sensor input options :-
18Vdc
Output 3
X1 1/8 DIN PID TEMPERATURE & PROCESS CONTROLLER
Fuzzy autotune and adaptive algorithms
Programmable alarm functions
Wide range of thermocouple inputs
IP65 front panel protection
Analogue output
Thermocouple
A/M
PT100
Current/voltage
mA
48 sq
mV - V
Output 1/2
Relay/relay
Relay/relay
Relay/relay
Relay/relay
Relay/relay
1
2
3
4
5
6
*
+
5
5
6
6
4
5
6
DIGITAL TEMPERATURE & PROCESS CONTROLLERS
Options
None
Setpoint programmer
RS485, programmer
None
RS485 comms
9
Input/output options :-
+
-
+
+
-
10
11
12
7
8
9
Current/voltage output, logic input
Current transformer input
Potentiometer input
Panel cut-out : 45 x 45
The X1 series microprocessor
based PID controllers are a cost
effective solution to heat-cool
applications. The X1 has up to 2
PID control outputs, programmable
alarm functions and optional serial
communications, remote setpoint
adjustment and ramp-dwell
functions. The IP65 rated 1/8 DIN
96x48 case has a clear dual LED
display showing the process value
and setpoint as well as function
indicators.
RS485 comms
100K
10A -
100A
10 -
(option)
150
Ramp and dwell functions
Remote set point facility
Dual 4 digit LED display
Heater break detection
Serial communications
Digital input
IL2
mA
Digital input
IL2
+
mV - V
14
13
15
16
17
18
100%
M5-3100-0000
M5-3100-1000
M5-3150-1000
M5-5100-0000
M5-5150-0000
Part Number
0%
+
+
+
+
-
-
+0.5
-0
L
N
12
10
11
12
10
11
12
10
11
Digital input IL1
Output 1
Output 2
(No IL2)
Supply
24
SPECIFICATION
Power supply :
Supply variation :
Input sensors :
Scale ranges :
RTDs :
Thermocouples :
Current:
Voltage :
Accuracy :
Operating modes : 1 PID or on/off loop with 2 or 3 alarms
Output 1 :
Output 2 :
Output 3 :
Output 4 :
Output 5 :
Serial interface :
Auxilliary supply :
Approvals :
Ambient temp :
Weight :
DIMENSIONS
CONNECTION DIAGRAM
RS485
Current
transfmr
PT100
Thermocouple
input
T/c W3%Re-W25%Re
T/c W5%Re-W26%Re
T/c Ni-NiMo18%
+
C
-
48
+
+
-
-
E-L-J t/c
10
12
12
11
11
1
2
3
4
5
6
7
8
9
100 - 240Vac @ 50/60Hz, 24Vac @50/60Hz, 24Vdc
-15% +10% of supply voltage
B, E, J, K, L, N, R, T, S thermocouples, PT100,
0/4 to 20mA, 0/10 to 50mV
PT100
PT100
B t/c
K t/c
N t/c
R t/c
S t/c
T t/c
0/4-20mA :
0/10 - 50mV :
+/- 0.25% of scale range +/- 1 digit (RTD & t/c)
+/- 0.1% of scale range (mA & mV)
2 PID or on/off heat-cool loops with 1or 2 alarms
SPST N.O. relay 2A/250Vac resistive or
24Vdc +/-20%, 30mA max for transmitter supply
Conforms to CE standards EN50081-1 and
EN50082-1 for emc and EN61010-1 for low voltage.
0 to 50ºC non condensing
250gms
Triac 1A/250Vac resistive
SPST N.O. relay 2A/250Vac resistive or
Triac 1A /250Vac resistive
SPDT N.O.Relay 2A/250Vac resistive
SSR drive 0-5Vdc +/-10%, 30mA max, non isolated
Analogue control output (optional)
RS485 isolated for Modbus/Jbus protocols
NC
NC
NC
NC
-99.9 to 300ºC
-200 to 600ºC
0 to 1800ºC
0 to 600ºC
0 to 1200ºC
0 to 1200ºC
0 to 1600ºC
0 to 1600ºC
-200 to 400 ºC
0 to 1100ºC
0 to 2000ºC
0 to 2000ºC
9
14
15
13
16
17
18
19
20
22
23
24
21
{ Configurable in engineering units
{ mA, mV, V, bar, psi, rH, ph
Panel cut-out : 92 x 45
-
+
NC
NC
NC
NC
NC
NC
NC
NC
Remote
setpoint
Output 5
+
-
110
26
27
32
33
25
28
29
30
31
34
35
36
+0.5
-0
Supply
+
-
+
Output 4
Output 3
Output1
Output2
24Vdc
L
N

Related parts for TC4810-52