DS6-34DSX055N0-N EATON CUTLER HAMMER, DS6-34DSX055N0-N Datasheet
DS6-34DSX055N0-N
Specifications of DS6-34DSX055N0-N
Related parts for DS6-34DSX055N0-N
DS6-34DSX055N0-N Summary of contents
Page 1
... SCR conduction period. This, in turn, controls the torque developed by the motor. After the motor reaches speed, a bypass contactor is ener- gized to bypass the SCRs. The DS6 is designed to fulfill the industrial service requirements of applications such as chiller starters, pump panels, and machine tools. This device meets all relevant specifications set forth by UL 508, IEC 60947-4-2, CE, C-Tick, and CSA ...
Page 2
... Mounting instructions The DS6 solid-state soft start controller is easy to mount. It does not require any special tools. To aid you with panel layout, refer to the dimension drawings shown in Figure 1 and Figure 2. Drill and tap holes per mounting hole/slot locations as shown. To mount the unit, use all the hardware specified in Table 1 of this leaflet ...
Page 3
... DS6-34DSX134N0-N 124 DS6-34DSX161N0-N 156 DS6-34DSX196N0-N 180 Maximum values are higher than allowed per NEC 430.52 and UL 508A 31.1. Table 5. Product Selection—kW Ratings According to IEC 60947-4-2 Rated Current Catalog Number (A) DS6-34DSX041N0-N 41 DS6-34DSX055N0-N 55 DS6-34DSX068N0-N 68 DS6-34DSX081N0-N 81 DS6-34DSX099N0-N 99 DS6-34DSX134N0-N 134 DS6-34DSX161N0-N 161 DS6-34DSX196N0-N 196 Maximum values are higher than allowed per NEC 430 ...
Page 4
... Vdc + and – terminals. Terminal connections are to be secured to a torque value of 3.6 lb-in. Control wiring is connected to the DS6 soft start controller by a 9-pin terminal block located on the front of the unit. Use the wiring diagrams in Figure 4, Figure 5, and the information in Table 7 as guides ...
Page 5
... DS6 series soft start controllers 24 Vdc power supply requirements The 24 Vdc power supply for your DS6 soft start controller must meet or exceed the following requirements: Minimum steady-state current: 1W (35 mA) • Minimum start command current: 2W (65 mA) • Minimum bypass contactor inrush current: 600 mA for 50 ms • ...
Page 6
... Applications with high starting torque are not suitable for DS6 soft start controllers. In some cases, over-sizing to a larger unit may be a solution. Consult Eaton’s Technical Resource Center at (877) 386-2273. ...
Page 7
... SCR fault Instructional Leafl et IL03901001E Use standard troubleshooting techniques to determine the cause of the trip. The DS6 does not provide any specific method of identifying the cause of the trip. Possible Solution Check for the following conditions: power supply failure and/or intermittent operation and volt- age stability ...
Page 8
... United States 877-ETN-CARE (877-386-2273) Eaton.com © 2009 Eaton Corporation All Rights Reserved Printed in USA Publication No. IL03901001E / Z8490 June 2009 DS6 series soft start controllers Table 10. LED Operation During Motor Start, Run, and Stop Conditions Ready Condition Motor Status Contacts 24 Vdc applied ...