MC485232 CARLO GAVAZZI, MC485232 Datasheet - Page 6

RS485 / RS232 PORT MODULE

MC485232

Manufacturer Part Number
MC485232
Description
RS485 / RS232 PORT MODULE
Manufacturer
CARLO GAVAZZI
Datasheet

Specifications of MC485232

Accessory Type
RS485 / RS232 Port Module
For Use With
WM3096 Type Smart Modular Power Analyzer

Available stocks

Company
Part Number
Manufacturer
Quantity
Price
Part Number:
MC485232
Manufacturer:
Carlo gavazzi
Quantity:
500
WM30 96
6
Output specifications (cont.)
Meters
Pulse output
Energy meter recording
Analysis principle
Harmonic measurement
Type of harmonics
Energy meters
Harmonic distortion analysis
IP configuration
BACnet-IP Port
Modbus Port
Client connections
Connections
Data
Total
Partial
Current
Voltage
Dynamic (reading only)
reading purpose and for
programming parameter
purpose)
Static IP / Netmask /
Default gateway
Fixed: BAC0h
Selectable (default 502)
Modbus only: max 5
simultaneously
RJ45 10/100 BaseTX
Max. distance 100m
System and phase
variables (BACnet-IP and
Modbus): see table “List of
variables...”
4 (9+1 digit)
4 (9+1 digit)
Connectable to total
and/or partial meters
Storage of total and partial
energy meters.
Energy meter storage
format (EEPROM)
Min. -9,999,999,999.9
kWh/kvarh
Max. 9,999,999,999.9
kWh/kvarh.
Up to the 32nd harmonic
Up to the 32nd harmonic
THD (VL1 and VL1-N)
The same for the other
phases: L2, L3.
THD (AL1)
The same for the other
phases: L2, L3.
FFT
Specifications are subject to change without notice
Note
Insulation
Energy Meters
System
Total energy meters
Partial energy meters
Static (reading and
writing only)
All the configuration
parameters (Modbus only).
With the rotary switch (on
the back of the basic unit)
in lock position the
modification of the
programming parameters
and the reset command by
means of the serial
communication is not
allowed anymore. In this
case just the data reading
is allowed.
See “Insulation between
inputs and outputs” table
+kWh, +kvarh, -kWh,
-kvarh
+kWh, +kvarh, -kWh,
-kvarh
The harmonic distortion
can be measured in 3-wire
or 4-wire systems.
Tw: 0.02 sec@50Hz
without filter
WM30 96 DS 271109