E5EN-Q3MT-500-N AC100-240 Omron, E5EN-Q3MT-500-N AC100-240 Datasheet - Page 11

Digital Temperature Controller

E5EN-Q3MT-500-N AC100-240

Manufacturer Part Number
E5EN-Q3MT-500-N AC100-240
Description
Digital Temperature Controller
Manufacturer
Omron
Datasheets

Specifications of E5EN-Q3MT-500-N AC100-240

No. Of Digits / Alpha
4
Meter Function
Temperature
Meter Range
-200°C To +2300°C
Digit Height
15.8mm
Power Consumption
10VA
Operating Temperature Range
-10°C To +55°C
Supply Voltage Max
240V
Supply Voltage Range
100VAC To 240VAC
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
External Connections
Controllers
• A voltage output (control output 1, for driving SSR) is not electrically insulated from the internal circuits. When using a grounding thermocouple,
• Consult with your OMRON representative before using the external power supply for the ES1B for any other purpose.
• 100 to 240 VAC
• 24 VAC/VDC (no polarity)
Long-life relay output
250 VAC, 3 A
(resistive load)
Voltage output
(for driving SSR)
Voltage output
(for driving SSR)
Current output
do not connect any of the control output terminals to ground. If the control output terminals are connected to ground, errors will occur in the
measured temperature values as a result of leakage current.
The voltage output (control output 2, for driving SSR) has basic insulation provided for the internal circuit.
Relay output
250 VAC, 5A
(resistive load)
12 VDC, 40 mA
Load: 600 Ω max.
Control output 2
Control output 1
0 to 20 mA DC
4 to 20 mA DC
Auxiliary output
Relay outputs
(resistive load)
250 VAC, 3 A
12 VDC, 21 mA
1, 2, 3
Input power supply
Auxiliary output 3
Auxiliary output 2
Auxiliary output 1
Control output 1
The E5@N-@@@T@ is set for a K-type thermocouple
(input type = 5) by default. An input error (s.err) will
occur if the input type setting does not agree with the
temperature sensor. Check the input type.
1 0
1
2
3
4
5
6
7
8
9
1 3
1 4
1 5
1 6
1 7
1 8
1 9
2 0
1 1
1 2
D O N O T
U S E
D O N O T
U S E
CT1/CT2 Control Output 2
Event Inputs
E V 2
TC/Pt
universal-input
C T 1
C T 2
E V 1
D O N O T
U S E
Control output 2
A
B
B
D O N O T
U S E
Analog input
V
D O N O T
U S E
External Power Supply
m A
D O N O T
U S E
External power supply
12 VDC, 20 mA
Option Units
E53-EN01
RS-232C
1 1
1 2
1 3
A heater burnout alarm, heater short alarm,
heater overcurrent alarm, or input alarm is
sent to the output to which the alarm 1
function is assigned.
S D
RD
S G
Communications
E53-EN03
RS-485
1 1
1 2
1 3
DO NOT USE
B (+)
A (−)
E5AN/E5EN
E53-AKB
Event inputs
1 1
1 2
1 3
CT1/CT2
E V 2
E V
11