AFPX-A21 PANASONIC EW, AFPX-A21 Datasheet - Page 14

Application Cassette

AFPX-A21

Manufacturer Part Number
AFPX-A21
Description
Application Cassette
Manufacturer
PANASONIC EW
Datasheet

Specifications of AFPX-A21

No. Of Analog Outputs
1
No. Of Analog Inputs
2
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
FP-X series
Other useful functions
* The limitation in a flash-ROM designates the number of rewrites to be
14
10,000, or the feasible number to be approx 30,000. However, rewriting
every second will generate a memory failure within a few hours.
The built-in 512kb flash-ROM can store a 32-k step pro-
gram as well as the comments and FPWIN Pro source
file.
Program update in a remote location is easy by simply
sending master memory for local installation.
As the master memory stores the password informa-
tion, password protection can be applied for program
transmission. Similarly, upload prohibition/permission
can be set up.
The built-in real-time clock enables periodical repeated
control and periodical data logging.
The programs and comments are stored in flash-ROM
requiring no backup batteries.
A backup battery (AFPX-BATT) is provided for data
and the real-time clock. 1 battery for C14, 2 for C30
and 3 for C60 can be attached. A 2-battery installation
can operate for a long time (10 years or more) without
maintenance. (The real-time clock does not work with-
out a battery.)
FP-X can store a program, comments, a total of 55
words of data and bit setting values in a flash memory
without a battery. All of the data and bits can be stored
by adding optional batteries, but writing into a flash-
ROM is possible without a battery by using applied in-
structions (F12, P13). Perfectly suited for data storage
of the setup values and recipes modified several times
a day. *
The master memory makes program transfer easy, and a real-time clock is also included
Programs can be saved without a backup battery, making maintenance easier
F-ROM data saving (data can be saved without a battery)
Flash-ROM
Reading
Writing
01/2008
FPWIN GR/Pro
Battery
holder
Master memory
Program
R9013
transfer
During the first scan, read one block
(2048 words) from the starting address of
DT0 at block number 0.
When R0 is turned on, write one block
(2048 words) starting from the address
DT0 at block number 0.
R0
F12 ICRD K0, K1, DT0
P13 ICWD DT0, K1, K0
To the field
operation
FP-X
Connector
Program
transfer
Password used
Upload prohibited set
Upload prohibited not set
Backup battery
for FP-X
(AFPX-BATT)
Password locked
FP-X
Upload prohibited
Upload permitted