WV468-2000.V1 EUROTHERM CONTROLS, WV468-2000.V1 Datasheet - Page 4

Isolation Amplifier

WV468-2000.V1

Manufacturer Part Number
WV468-2000.V1
Description
Isolation Amplifier
Manufacturer
EUROTHERM CONTROLS
Datasheets

Specifications of WV468-2000.V1

Width
0.5"
Peak Reflow Compatible (260 C)
Yes
Output Accuracy
± 0.05% Of FS
Signal Input Type
Selectable Current Or Voltage
Supply Voltage
24VDC
Configuration Setup
DIP Switch
Iso-amp Mounting Type
DIN Rail
Display Alarm Type
2 Relay
Input Accuracy
± 0.015% Of FS
Leaded Process Compatible
Yes
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Specifications
Inputs
RMS Voltage Ranges
RMS Current Ranges
Frequency Range
Linearity
Input Ranges
Turn-Up/Turn-Down
Eurotherm Controls
741-F Miller Drive
Leesburg, VA 20175-8993
703-443-0000
info@eurotherm.com
actionio.com
Ordering Information
Specify:
1. Model:
2. Optional Custom Factory Calibration (specify C620,
3. Accessories.
Accessories
All WV Series modules will mount on standard TS35
(model MD03) DIN rail. In addition, the following acces-
sories are available:
WVC16
MD03
WV905
H910
H915
MB03
C650
50mV, 150mV, 500mV, 5V, 20V, 50V, 150V,
250V @ ±0.15% of FS accuracy
Impedance: >100k ohms
Over-voltage 275Vrms
20mA, 100mA @ ±0.15% of FS accuracy
Impedance: 10 ohms typical
Over-current: 200mA, protected by self-
Over-voltage: 60V
40 to 400Hz
±0.1% of span, typical
Pushbutton adjustable
Effective zero offset: > 95%
Effective span turndown: > 95%
80% (90% to ±0.25%)
WV468-2000
see required settings under "Calibration, page 2).
Action Instruments
resetting fuse
Communications Interface
TS35 x 7.5 DIN Rail (2 meters)
24VDC Power Supply (0.5 Amp)
24VDC Power Supply (1 Amp)
24VDC Power Supply (2.3 Amp)
End Bracket for MD03
Utility software for WVC16
Barber-Colman
Output Ranges
Output Accuracy
Response Time
Stability
Output Ripple
Output Impedance
Common Mode Rejection
Output Drive
Dimensions
Dimensions are in millimeters (inches)
0-10VDC
0-20mA, 4-20mA
±0.05% of Full Scale
100mSec typical
±100ppm of span/°C
0.2% of span, or 5mVrms, whichever is greater
Voltage Output: <10 ohms (source impedance)
Current Output: >100k ohms
60Hz: >90dB
DC: >120dB
Voltage Output: 10mA, max
Current Output: 20V compliance @ 20mA
(1k ohms max)
Eurotherm Chessell
721-0864-00-C 07/06 Copyright© Eurotherm, Inc 2006
Factory Assistance
For additional information on calibration, operation and
installation contact our Technical Services Group:
actionsupport@eurotherm.com
703-669-1318
Temperature Range
Power
Isolation
Host Module Interface
Size
Operating: 0° to 60°C (32 to 140°F)
Storage: -20° to 85°C (-4 to 185°F)
9 to 30VDC
1W typical, 2W maximum
Input to Output to Power: 1800VDC
IR Link
DIN rail case – refer to Dimensions drawing
Eurotherm Controls

Related parts for WV468-2000.V1