WV478-2000.V1 EUROTHERM CONTROLS, WV478-2000.V1 Datasheet - Page 4

Isolation Amplifier

WV478-2000.V1

Manufacturer Part Number
WV478-2000.V1
Description
Isolation Amplifier
Manufacturer
EUROTHERM CONTROLS
Datasheets

Specifications of WV478-2000.V1

Width
0.5"
Output Accuracy
± 0.05% Of FS
Signal Input Type
Selectable Frequency
Supply Voltage
24VDC
Configuration Setup
DIP Switch
Iso-amp Mounting Type
DIN Rail
Display Alarm Type
2 Relay
Rohs Compliant
NA
Input Accuracy
± 0.015% Of FS
Specifications
Inputs
Outputs
Eurotherm Controls
741-F Miller Drive
Leesburg, VA 20175-8993
703-443-0000
info@eurotherm.com
actionio.com
Ordering Information
Specify:
1. Model:
2. Optional Custom Factory Calibration (specify C620,
3. Accessories.
Accessories
All WV Series modules will mount on standard TS35
(model MD03) DIN rail. In addition, the following acces-
sories are available:
WVC16
MD03
WV905
H910
H915
MB03
C650
Frequency Input Range
Minimum Input Span
Amplitude (switch selectable)
Voltage: 0 to 10VDC
Drive: 10mA
Current: 0 to 20mA
WV478-2000
see required settings under "Calibration, page 2).
Action Instruments
0 to 10kHz
2Hz
Low Range: 150mVp to 50Vrms
High Range: 500mVp to 150Vrms
Source Impedance: 10 ohms
Source Impedance: >100k ohms
Compliance: 20V@20mA (1k ohms max)
Communications Interface
TS35 x 7.5 DIN Rail (2 meters)
24VDC Power Supply (0.5 Amp)
24VDC Power Supply (1 Amp)
24VDC Power Supply (2.3 Amp)
End Bracket for MD03
Utility software for WVC16
Barber-Colman
Output Accuracy
Response Time
Stability
Common Mode Rejection
Isolation
ESD Susceptibility
Power
Dimensions
Dimensions are in millimeters (inches)
±0.05% of full scale local range
100mSec (10-90%) typical
±100ppm of full scale/°C (±0.01%/°C)
60Hz: >90dB
DC: >120dB
Input to Output to Power: 1800VDC
Capable of meeting IEC801-2 level 3 (8kV)
9 to 30VDC
1W typical, 2W maximum
Eurotherm Chessell
721-0806-00-F 09/04 Copyright© Eurotherm, Inc 2004
Factory Assistance
For additional information on calibration, operation and
installation contact our Technical Services Group:
actionsupport@eurotherm.com
703-669-1318
Host Module Interface
Size
Temperature Range
Humidity Range
Agency Approvals (EMC & Safety)
IR Link
DIN rail case – refer to Dimensions drawing
Operating: 0°C to 60°C (32°F to 140°F)
Storage: -25°C to 85°C (-13°F to 185°F)
Operating: 15% to 95% RHNC @ 45°C
Storage: 90% RHNC @60°C for 24 hrs
CE, EN50081-1, EN50082-2, EN61010
CSA C22.2, No. 0-M91, 142-M1987
UL508
Eurotherm Controls

Related parts for WV478-2000.V1