MTL5513 MTL SURGE TECHNOLOGIES, MTL5513 Datasheet

no-image

MTL5513

Manufacturer Part Number
MTL5513
Description
ISOLATED BARRIER, DIG I/P
Manufacturer
MTL SURGE TECHNOLOGIES
Datasheet

Specifications of MTL5513

Input Type
Proximity Detectors
Output Type
Transistor
Approval Bodies
ATEX
External Depth
123.6mm
External Length / Height
109.8mm
External Width
15.8mm
Isolation Input
Isolated
Mounting Type
DIN
Svhc
No SVHC (15-Dec-2010)
Rohs Compliant
NA
Lead Free Status / RoHS Status
na
The MTL5513 enables two solid-state outputs in the safe area to
be controlled by two switches or proximity detectors located in the
hazardous area. The Ch1/Ch2 output transistors share a common
terminal and can switch +ve or -ve polarity signals. Independent output
phase reversal and line fault detection are enabled via switches for
each output. LFD indication is provided on the top of the module.
SPECIFICATION
See also common specification
Number of channels
Location of switches
Location of proximity detectors
Hazardous-area inputs
Voltage applied to sensor
Input/output characteristics
Line fault detection (LFD) (when selected)
Note: Resistors must be fitted when using the LFD facility with a contact input
500Ω to 1kΩ in series with switch
20kΩ to 25kΩ in parallel with switch
Phase reversal
Safe-area outputs
MTL5513 SWITCH/
PROXIMITY DETECTOR
INTERFACE
two-channel, with line fault detection
and phase reversal
Two
Zone 0, IIC, T6 hazardous area
Div. 1, Group A hazardous location
Zone 0, IIC, T4–6 hazardous area if suitably certified
Div. 1, Group A hazardous location
Inputs conforming to BS EN60947–5–6:2001 standards for
proximity detectors (NAMUR)
7 to 9V dc from 1kΩ ±10%
Normal phase
Hysteresis: 200µA (650Ω) nominal
User-selectable for each channel via switches on the side of the
unit. Line faults are indicated by an LED for each channel.
Open-circuit alarm on if Iin < 50µA
Open-circuit alarm off if Iin > 250µA
Short-circuit alarm on if Rin < 100Ω
Short-circuit alarm off if Rin > 360Ω
Independent for each channel, user-selectable
Floating solid-state outputs compatible with logic circuits
Operating frequency:
Max. off-state voltage:
Max. off-state leakage current:
Max. on-state resistance:
Max. on-state current:
Outputs closed if input > 2.1mA (< 2kΩ in input circuit)
Outputs open if input < 1.2mA (> 10kΩ in input circuit)
EUROPE (EMEA)
AMERICAS
ASIA PACIFIC
E-mail: enquiry@mtl-inst.com
Tel: +44 (0)1582 723633
Tel: +1 281 571 8065
Tel: +65 6 487 7887
Web site: www.mtl-inst.com
dc to 500Hz
± 35V
± 50µA
25Ω
± 50mA
Fax: +44 (0)1582 422283
Fax: +1 281 571 8069
Fax: +65 6 487 7997
The given data is only intended as a product description and should not be re-
garded as a legal warranty of properties or guarantee. In the interest of further
technical developments, we reserve the right to make design changes.
* Signal plug HAZ1-3 is required for access to this function
LED indicators
Maximum current consumption
Power dissipation within unit
Safety description (each channel)
Hazardous area
Terminal
Green: power indication
Yellow: two: channel status, on when outputs are on
Red: two: LFD indication, on when line fault detected
27mA at 24V
0.65W typical at 24V, with 10mA loads
0.78W max. with 50mA loads
V
o
=10.5V I
10
11
12
13
1
2
3
4
5
6
W
W
W
W
o
=14mA P
Function
Input –ve (Ch 1)
Input +ve (Ch 1)
To earth leakage detector*
Input –ve (Ch 2)
Input +ve (Ch 2)
To earth leakage detector*
Output (Ch 2)
Output (Ch 1/Ch 2)
Output (Ch 1)
Supply –ve
o
=37mW U
Safe area
m
= 253V rms or dc
EPS5513-2
Jan 2009

Related parts for MTL5513

MTL5513 Summary of contents

Page 1

... INTERFACE two-channel, with line fault detection and phase reversal The MTL5513 enables two solid-state outputs in the safe area to be controlled by two switches or proximity detectors located in the hazardous area. The Ch1/Ch2 output transistors share a common terminal and can switch +ve or -ve polarity signals. Independent output phase reversal and line fault detection are enabled via switches for each output ...

Page 2

MTL5500 SERIES COMMON SPECIFICATION Please go to our website at www.mtl-inst.com for the latest information regarding safety approvals, certificates and entity parameters. Connectors Each MTL5500 unit is supplied with signal connectors, as applicable. When using crimp ferrules for the hazardous ...

Related keywords