CS1W-CN225 Omron, CS1W-CN225 Datasheet - Page 127

no-image

CS1W-CN225

Manufacturer Part Number
CS1W-CN225
Description
"CABLE,PROG
Manufacturer
Omron
Datasheet

Specifications of CS1W-CN225

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Installation Precautions
Improving Noise
Resistance
PC Orientation
If the I/O wiring and power cables must be placed in the same duct, they must
be shielded from each other using grounded steel sheet metal.
Reduce the effects of noise by observing the following points.
When installing the CQM1H in the control panel, always mount the Units so
that the ventilation openings are facing up. Also, there must be at least a 20-
mm space both above and below the PC.
• Do not mount the PC in a control panel containing high-voltage equip-
• Install the PC at least 200 mm (6.5 feet) from power lines.
• Ground the mounting plate between the PC and the mounting surface.
Power lines
CQM1H
ment.
200 mm min.
PC I/O wiring
200 mm min.
Correct
Wrong
PC power supply
control wiring
and general
Ground to 100
Power lines
Wrong
or less
Steel sheet metal
200 mm min.
Section 4-2
105

Related parts for CS1W-CN225