Connecting Electrode Holder and Electrode Band
Connect the connecting nut to the Electrode section as shown in the illustration below
and secure the connecting nut with the clamp screw. Insert the Electrode Band into the
lower hold of the connecting nut, and tighten the two clamp screws so that the
conductor in the Electrode Band will come into contact with the connecting nut. Then
mount the Electrode Holder to the Electrode section and secure them with two
mounting screws, which are provided with the model.
Mounting Weight (2)
Install Electrode Band Weights in three
positions. The Electrode Band Weights
work as short, medium, and long
Electrodes, allowing the Electrode Band to
detect high, medium, and low levels of
liquid.
In purified city water, if the distance between the long Electrode (E3) and short Electrode (E1) is more than 50 cm, install another
Electrode Band Weight as E3 in the vicinity of E1 at intervals of 15 to 20 cm, referring to Mounting Weight (2) above. An Insulation Cap
is not needed for the long Electrode.
Electrode Bands
Connecting
nut
Electrode
section
housing
Electrode
Band
Electrode
Holder
Drip-proof
cover
Secure the Weight
with needle screws.
Insulation Cap
Insulation Cap
Mounting Insulation Cap
Cover each Electrode Band Weight with an
Insulation Cap so as to prevent false
detection due to contact between the
Electrode and tank. Deform the Insulation
Cap to an ellipsoid before installing it on
the Electrode Band Weight.
Connecting nut
(SUS304)
End cap
Electrode
band
F03-09 Insulation Cap (PVC)
E3 (long)
E2 (medium)
Connect the Electrode
wire to the connecting nut.
E1 (short)
E3 (long)
Securing
screws
Add another E3 (long Electrode)
Weight if this distance is more than 50
cm.
Mounting Weight(1)
To mount an Electrode Band Weight on an
Electrode Band, firmly tighten the two
screws A or B. The needle screws will
come into contact with the electrode wire
(conductor) allowing the Electrode Band
Weight to become an electrode plate. (Be
sure to use screw holes A or B.). The
Electrode has guides for connecting
screws as shown by the arrows below so
that connecting screws can be properly
inserted into the conductor.
Mounting End Cap
Cover the Electrode Band end and apply
the Adhesive sold separately to prevent
water from entering between the sheath
and the the End Cap.
Electrode Band
B
F03-09 End Cap (rubber)
F03-07 Weight (SIS304)
A
F03-10
Adhesive
Guides