CONDUCTIVE LEVEL CONTROLLER, 230V

61FD21T 100-240AC

Manufacturer Part Number
61FD21T 100-240AC
Description
CONDUCTIVE LEVEL CONTROLLER, 230V
Manufacturer
Omron
Datasheet

Specifications of 61FD21T 100-240AC

Supply Voltage
230VAC
Response Time
10s
Power Consumption
5VA
Svhc
No SVHC (15-Dec-2010)
Approval Bodies
CE
Contact Configuration
Self-hold
Contact Current Max
6A
Ordering Information
■ List of Models
Specifications
Rated voltage
Operating voltage range
Voltage between electrodes
Power consumption
Operating resistance
Reset resistance
Response time
Cable length
Control output
Indicators
Ambient temperature
Ambient humidity
Elevation
Insulation resistance
Dielectric strength
Vibration resistance
Shock resistance
Installation environment
Safety standards
EMC
Conductive Level Controller
24 VAC/DC
100 to 240 VAC
Supply voltage
24 VAC, 50/60 Hz, or 24 VDC
100 to 240 VAC, 50/60 Hz
85% to 110% of rated voltage
6 V p-p (approx. 20 Hz)
24 VDC: 2 W max.
24 VAC: 4 VA max.
100 to 240 VAC: 5 VA max.
10 kΩ to 100 kΩ (variable)
250 kΩ max.
Approx. 0.1 to 10 s (variable)
100 m max. with completely insulated (600 V) cabtire cable with 3 conductors (0.75 mm
6 A at 250 VAC for resistive load at 20°C, 1 A at 250 VAC for inductive load cosφ = 0.4 at 20°C
Green LED: Power, Yellow LED: Control output
Operating: −20 to 60°C, Storage: −30 to 70°C (with no condensation or icing)
Operating: 25% to 85%, Storage: 25% to 85%
2,000 m max.
100 MΩ min. (at 500 VDC) between power supply section, electrode section, and contact section
2,000 VAC 50/60 Hz for 1 min between power source section, electrode section, and contact section
Vibration of 10 to 55 Hz and acceleration of 50 m/s
100 m/s
Overvoltage Category II, Pollution Degree 2
EN61010-1
EN61326 Industrial applications
2
3 times each in 6 directions on 3 axes
61F-D21T-V1 24 VAC/DC
61F-D21T-V1 100 to 240 VAC
Model
2
for 5 min. 10 times each in X, Y, and Z directions
61F-D21T-V1
2
)
2

Related parts for 61FD21T 100-240AC