8080-1-0-0-0-0 WEST INSTRUMENTS, 8080-1-0-0-0-0 Datasheet

INDICATOR, TEMPERATURE

8080-1-0-0-0-0

Manufacturer Part Number
8080-1-0-0-0-0
Description
INDICATOR, TEMPERATURE
Manufacturer
WEST INSTRUMENTS
Datasheet

Specifications of 8080-1-0-0-0-0

Thermocouple Type
J, K, R, S, T, B, N
Operating Temperature Max
55°C
Operating Temperature Min
0°C
Output Voltage Max
30VDC
Accuracy
± 0.1%
Accuracy %
0.1%
Approval Bodies
CE, UL, ULC
West 8080 1/8 DIN Dual Colour Indicator
Technical Data
Features
Output Configuration
Alarm Types
Viewable Values
Human Interface
Temperature Version
Input
Impedance
Accuracy
Sampling
Sensor Break Detection
DC Process Version
Input
Scaling
Impedance
Accuracy
Sampling
Sensor Break Detection
Totalising of PV by Interval
Transmitter Power Supply
Outputs & Options
Alarm 1
Alarm 2
Retransmit Output
Digital Input
Communications
Operating & Environmental
Temperature & RH
Power Supply
Front Panel Protection
Approvals and Certification
Up to 3 total., max 2 for Alarms, max 1 for retransmission of PV
Process high, process low, direct acting, process high, process low reverse and logical OR
Process variable, alarm values, maximum value, minimum value and elapsed time since
reset
4 button operation, 5 digit 18mm high colour change display, plus set-up and alarm
indicators
J, K, R, S, T, B, & N Thermocouple, 3 or 4 Wire PT100, 50Ω per lead maximum (balanced)
>100MΩ for Thermocouple
+/- 0.1% of input span +/- 1 LSD (T/C CJC better than 0.5°C)
4 per second, 14 bit resolution
<2 secs, all alarms activate
0-20/4-20/10-50mA, 0-5/1-5/0-10/2-10V, +/-100mV, +/-1V, +/-10V
-19999 to99999, dec point as required. Up to 10 scaling points for non-linear applications
>100KΩ for mV range, >950KΩ for V ranges, 10Ω for 20mA ranges and 1Ω for 50mA range
+/- 0.01% of input span typical (+/- 0.05% max) +/- 1 LSD
10 per second, 14 bit resolution
<2 secs (except zero based ranges), all alarms activate
Seconds, minutes or hours
20-28V DC (24V nominal), max load 910Ω (22mA at 20V). Fitted as standard
Open collector NPN transistor (30VDC 100 mA max) and relay (Contacts SPDT 3Amp
Open collector NPN transistor (30VDC 100mA max) fitted as standard. Optional relay
(Contacts SPDT 3Amp resistive at 240VAC/5Amp at 110V), non-latching
0-20/4-20mA into 500Ω max, 0-10/0-5V into 500Ω min. Accuracy typically +/- 0.25% 250mS
update
External security lock (also Tare function on Process Version). Volt free or TTL compatible
2 wire RS485, 1200 to 9600 baud. ASCII protocol
0 to 55°C (-20 to 80°C storage), 20% to 95%RH non-condensing
100 to 240V 50/60Hz 7.5VA (optional 20 to 50V AC 7.5VA/22 to 55V DC 5W)
IEC IP66 (Behind panel protection is IP20)
CE, UL & UlC
The West 8080 offers high accuracy temperature or process inputs.
The custom-designed display is larger than other instruments of this
size, and can be set to change colour to indicate alarm status.
Large Five Digit Display
Colour Change On Alarm
Min/Max Value Hold
2 Process Alarms
Product Specification
Security Lock
Process Transmitter PSU
PV retransmit option
RS485 comms option

Related parts for 8080-1-0-0-0-0

8080-1-0-0-0-0 Summary of contents

Page 1

... IEC IP66 (Behind panel protection is IP20) Approvals and Certification CE, UL & UlC Product Specification The West 8080 offers high accuracy temperature or process inputs. The custom-designed display is larger than other instruments of this size, and can be set to change colour to indicate alarm status. • ...

Page 2

... Option Slot 2 No option fitted Analogue DC Re-Transmit PV In accordance with our policy of continuous improvement, we reserve the right to change specifications from those shown in this document. 8080 Spec Sheet – 08/03 West Instruments Tel: +44 (0) 1273 606271 The Hyde Business Park Fax: +44 (0) 1273 609990 ...

Related keywords