DMFC12 400VAC UA (UNITED AUTOMATION), DMFC12 400VAC Datasheet

no-image

DMFC12 400VAC

Manufacturer Part Number
DMFC12 400VAC
Description
DUAL MODE FIRING CIRCUIT, 400V
Manufacturer
UA (UNITED AUTOMATION)
Datasheet

Specifications of DMFC12 400VAC

Approval Bodies
CE
External Depth
114mm
External Length / Height
55mm
External Width
70mm
Mounting Type
DIN Rail
Operating Frequency
400Hz
Operating Temperature Max
+75°C
Operating Temperature
RoHS Compliant
ORDER DETAILS
Specification
AC input supply (nominal)
DC input supply
Signal Span maximum
Signal Zero offset
Thyristor line voltage
Signal input resistance
Manual potentiometer
Trigger pulse height
Limit feedback input
Trigger isolation voltage
Trigger pulse rating
Soft start
Storage temperature
Operating temperature
INSTALLATION
For CT Information see Datasheets X10391 (32A) and X10424 (240A)
Connections
This unit has simple clamp type terminal connectors for all auxiliary-wiring requirements.
Fastening
The unit is secured by DIN-rail mounting feet for quick installation/removal
Fusing
See SRA Data sheet X10255 for further information. Other external supplies should be fused
accordingly.
CE Marking
This family carries a “CE” marking. These burst fire controllers do not normally require a
remote filter. For more information contact our sales desk.
available on request.
Signal Span minimum
DMFC12
UNITED AUTOMATION LIMITED
Page No. 4 of 4
1Southport Business Park
Kew
Southport, PR8 4HQ
ENGLAND
18 to 24V AC (RMS) @ 100mA
24V DC
0-100%
0-100%
-50 to 50%
12 to 480V AC (RMS) @ 50/60Hz
5000Ω ± 20%
1KΩ, 5kΩ or 10kΩ
8V open circuit
0.6 - 30V DC
2500V AC (RMS)
250mA in to 10Ω
(adjustable) 0-30 seconds
0°C to +85°C
0°C to 75°C
Issue 1
A31451 (110vAC)
A31452 (230vAC)
A31453 (400vAC)
Tel: 0044 (0) 1704 – 516500 Main
Fax: 0044 (0) 1704 – 516501
Enquiry@united-automation.com
www.united-automation.com
Date 27/07/08
A Declaration of Conformity is
C/W SOFT START AND CURRENT LIMIT
DUAL MODE FIRING CIRCUIT
Dual-Mode Firing Circuit (DMFC12) Features
Phase angle and burst fire modes of control
Soft-start (0-30s)
Current limit (using external CT or shunt/Hall-effect
device)
Enable input (volt-free)
0-5V/0-10V, 0-20mA/4-20mA or potentiometer input
signal
24VDC or 18-24VAC supply
Output power span and zero adjustment
Frequency tracking (4Hz – 400Hz)
Pulse transformer output
Power and status LEDs
Phase-loss detection
DMFC12
RoHS Compliant
2002/95/EC
Directive
DMFC12
X10732

Related parts for DMFC12 400VAC

DMFC12 400VAC Summary of contents

Page 1

Specification AC input supply (nominal 24V AC (RMS) @ 100mA DC input supply 24V DC Signal Span minimum 0-100% Signal Span maximum 0-100% Signal Zero offset -50 to 50% Thyristor line voltage 12 to 480V AC (RMS) @ ...

Page 2

Power Supply The DMFC12 accepts an 18-24VAC or 24VDC supply. Observe the polarity when using a DC supply. The unit consumes 200mA MAX @ 24VDC. Power Output Modes These Modes must be set before power up. The DMFC12 can be ...