SDU 10-24 SOLA HEVI DUTY, SDU 10-24 Datasheet - Page 3

UPS, 30V, 240VA

SDU 10-24

Manufacturer Part Number
SDU 10-24
Description
UPS, 30V, 240VA
Manufacturer
SOLA HEVI DUTY
Datasheet

Specifications of SDU 10-24

Capacity (va / W)
240VA
Input Voltage
22.5V DC To 30V DC
Output Voltage
30V
Backup Time - Full Load
14min
Length
116mm
Width
77mm
Height
124mm
Weight
1.65lb
Output Type
Variable
Output Current 1
10A
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
SDU DC UPS Power Modules Specifications
Notes:
50
Nominal Input Voltage
Input Voltage Range
Input Fuse
Nominal Output Voltage
Output Voltage Range
Output Current
Current Limit
Input Protection
Overload Protection
Short Circuit
Type
Charging Current
Typical Recharge Time
(to 90% of full capacity)
Back-up Time (full load)
Protection
Net Weight - lbs (kg)
Dimensions H x W x D - in. (mm)
Battery Low
Overload
Audible Noise
Power Module Operating Temperature
Storage Temperature
Humidity
Max Elevation
Shock & Vibration
US Standard
Canadian Standard
CE
MTBF
Output
Mounting
Connections
Relay Contact Terminal Connections
Case
Free Space
3
1. See Battery Back-up Times on next page.
2. DC UPS System includes one power module (SDU 10-24 or SDU 20-24) and one or more battery modules (SDU 24-BAT or SDU 24BATEM)
Specification
1
Directive 2004/108/EC: EN 62040-2 Category C2 EN 55022 Class A + A1 + A2, CISPR 22 Class A (2005), IEC 61000-3-
2, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6 + A1, IEC 61000-4-8, IEC 61000-2-2
Simple snap-on system for DIN Rail TS35/7.5 or TS35/15 or chassis-mounted, optional screw mounting set SDU-PMBRK.
contact Technical Services at (800) 377-4384 with any questions.
Uninterruptible Power Systems
Outputs are capable of providing high currents for short periods of time for inductive load startup or switching.
UPS Shutdown when battery voltage drops below 22V, to prevent the complete depletion of the battery,
Visit our website at www.solaheviduty.com or
Fusing may be required for wire/loads if 2x Nominal O/P current rating cannot be tolerated.
Input & Output: IP20-rated screw terminals, connector size range: 16-12 AWG (0.5-4 mm
Fully enclosed metal housing with ventilation grid to keep out small particles.
14 minutes
SDU 10-24
20 mm above and 35 mm below, 20 mm left and right, 10 mm in front
IP20 screw terminals; connector size range: 24-16 AWG (0.34-4mm
10A
12A
DC UPS System
CAN/CSA C22.2 No 107.1-01, CAN/CSA C22.2 No. 60950-1
Continuous current overload allows for reliable fuse tripping
Battery Module
UL 60950-1, UL508, FCC Part 15, Subpart B, Class A
Environment
Installation
Protection
Physical
Low Voltage Directive IEC 60950-1 (CB Scheme)
General
Output
Alarm
Sealed, maintenance-free lead acid batteries.
Input
12 Hours for each additional Battery Module
Fuse for overload & short circuit protection
Rapid Audible Indicator every 1 second
short circuit protection by a 30A fuse.
4.88 x 3.02 x 4.55 (124 x 77 x 116)
2
> 200,000 Hours, MIL-STD 217F
for copper conductors rated 90
<40 dBA (1 meter from surface)
Safety
UPS output cut off immediately
24 Hours for 2 Battery Module
8 Hours for 1 Battery Module
Continuous Audible Indicator
Electrical Circuit Protection
3500 meters (11,483 feet)
According to ISTA 2A
-20
-20
22.5 - 30 Vdc
22.5 - 30 Vdc
DC Fuse 30A
1.65 (0.75)
o
o
24 Vdc
24 Vdc
C to +50
C to +70
0-95%
0.5 A
o
o
C
C
o
.
SDU 20-24
4 minutes
20A
22A
2
)