RBC-12/17-D48P-C Murata Power Solutions Inc, RBC-12/17-D48P-C Datasheet

DC/DC

RBC-12/17-D48P-C

Manufacturer Part Number
RBC-12/17-D48P-C
Description
DC/DC
Manufacturer
Murata Power Solutions Inc
Series
RBC-12/17-D48r
Type
With UVLOr
Datasheet

Specifications of RBC-12/17-D48P-C

Product
Isolated
Output Power
210 W
Input Voltage Range
36 V to 75 V
Input Voltage (nominal)
48 V
Number Of Outputs
1
Output Voltage (channel 1)
12 V
Output Current (channel 1)
17 A
Isolation Voltage
2250 V
Package / Case Size
Quarter Brick
Output Voltage
12 V
Dc / Dc Converter O/p Type
Fixed
No. Of Outputs
1
Input Voltage
36V To 75V
Power Rating
210W
Output Current
17A
Supply Voltage
48V
Dc / Dc Converter Case Style
DIP
Voltage - Input (min)
36V
Voltage - Input (max)
75V
Power (watts) - Manufacture Series
210W
Power (watts) - Max
204W
1st Output
12 VDC @ 17A
2nd Output
-
3rd Output
-
Voltage - Isolation
2.25kV (2250V)
Mounting Type
Through Hole
Package / Case
5-DIP Module, 1/4 Brick
Size / Dimension
2.30" L x 1.45" W x 0.42" H (58.4mm x 36.8mm x 10.7mm)
Operating Temperature
-40°C ~ 85°C
Efficiency
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
FEATURES
www.murata-ps.com
Up to 210 Watts total output power
Up to 93% ultra-high effi ciency @ full load
48V Input ( up to 36-75V range)
12V/17A Output for Regulated Intermediate Bus
Architectures (RIBA) with POL converters
Synchronous-rectifi er topology
225kHz fi xed switching frequency
Fully isolated, 2250Vdc (BASIC)
2.3" x 1.45" x 0.42" quarter brick
Stable no-load condition
Thermal shutdown
Fully I/O protected
Certifi ed to UL/IEC/EN 60950-1 and CSA C22.2
No.60950-1-07, 2nd edition
Typical unit
www.murata-ps.com/rohs
For full details go to
 
Optimized for distributed power Regulated Intermediate Bus Archi-
tectures (RIBA), the RBC DC/DC bus converter series offer regulated
outputs (±1.5%) in an industry-standard quarter brick open frame
package.
PRODUCT OVERVIEW
The present trend in distributed power architec-
tures (DPA) requires both high effi ciency and some
regulation of the output voltage to reduce the risk
of under voltage dropout. Earlier unregulated bus
converters were simply ratiometric “DC transform-
ers.” The fully isolated (2250Vdc) RBC series accept
a wide range 36 to 75 Volt DC input (48V nominal)
and convert it to an output of 12Vdc. This output
then drives point-of-load (PoL) converters such as
our Okami, LSN, LEN, LSM or LQN series which
feature precise load regulation. Applications include
48V-powered datacom and telecom installations,
base stations, cellular telephone repeaters and
embedded systems. Low overall height of 0.42"
(10.7 mm) fi ts tight card cages.
www.murata-ps.com
Figure 1. Simplifi ed Block Diagram
Output (V)
12
Quarter Brick, Regulated Bus Converters
RBC-12/17-D48 Series
Current (A)
17
The RBC’s synchronous-rectifi er topology and fi xed
frequency operation means excellent effi ciencies.
“No fan” or zero airfl ow applications may use the
optional base plate for cold surface mounting or
natural-convection heatsinks.
A wealth of electronic protection features include
input undervoltage (UV) lockout, output current limit,
short circuit hiccup, overtemperature shutdown
and output overvoltage. Available options include
positive or negative polarity remote On/Off control
and the baseplate. Assembled using ISO-certifi ed
automated surface-mount techniques, the RBC
series includes all UL and IEC emissions, safety and
fl ammability certifi cations.
11 Apr 2011 MDC_RBC-12/17-D48.A03 Page 1 of 9
Typical topology is shown.
email: sales@murata-ps.com
Nominal Input (V)
48

Related parts for RBC-12/17-D48P-C

RBC-12/17-D48P-C Summary of contents

Page 1

... For full details go to www.murata-ps.com/rohs Output (V) 12 Optimized for distributed power Regulated Intermediate Bus Archi- tectures (RIBA), the RBC DC/DC bus converter series offer regulated outputs (±1.5 industry-standard quarter brick open frame package. PRODUCT OVERVIEW The present trend in distributed power architec- tures (DPA) requires both high effi ...

Page 2

... RoHS-6 hazardous substance compliant (does not claim EU RoHS exemption 7b–lead in solder) Note: Some model number combinations may not be Optional Baseplate, available. Contact Murata Power Solutions for special order ordering assistance. email: sales@murata-ps.com 11 Apr 2011 MDC_RBC-12/17-D48.A03 Page Package Case Pinout C49 P65 ...

Page 3

... Copper alloy with gold plate over nickel underplate 1 ounce (28.4 grams) Absolute Maximum Ratings 75 Volts 100 Volts None, see notes. Install external fuse. Current limited. Devices can withstand an indefi nite output short circuit without damage. –55 to +125°C +280°C email: sales@murata-ps.com 11 Apr 2011 MDC_RBC-12/17-D48.A03 Page ...

Page 4

... WITH SEATING PLANE WITHOUT Dimensions are in inches (mm shown for ref. only). Third Angle Projection Tolerances (unless otherwise specified): .XX ± 0.02 (0.5) .XXX ± 0.010 (0.25) Angles ± 2˚ Components are shown for reference only. email: sales@murata-ps.com 11 Apr 2011 MDC_RBC-12/17-D48.A03 Page ...

Page 5

... SHIPPING TRAYS AND BOXES, THROUGH-HOLE MOUNT SHIPPING TRAY DIMENSIONS RBC modules are supplied in a 15-piece ( shipping tray. The tray is an anti-static closed-cell polyethylene foam. Dimensions are shown below. 252.0 +.000 [9.92] -.062 15.875 [0.625] 60.96 [2.400] 18.67 [0.735] Notes All dimensions in millimeters [inches] 4. Tolerances unless otherwise specifi ...

Page 6

... VIN = 36V 5 7.5 10 12.5 Load Current (A) Maximum Power Temperature Derating at Sea Level Vin = 48 (air fl ow from Pin 1 to Pin 3 on PCB, with baseplate) 65 LFM 100 LFM 200 LFM 300 LFM 400 LFM Ambient Te mperature (°C) email: sales@murata-ps.com 11 Apr 2011 MDC_RBC-12/17-D48.A03 Page 17 ...

Page 7

... Ta=+25°C, Scope BW=20MHz) Stepload Transient Response (Vin=48V, Iout=25-75-25% of Imax, Cout=1 & 10uF, Output Ripple and Noice (Vin=48V, Iout=17A, Cout=1 & 10uF, Ta=+25°C, Scope BW=20MHz) www.murata-ps.com RBC-12/17-D48 Series Quarter Brick, Regulated Bus Converters Ta=+25°C, Scope BW=20MHz) email: sales@murata-ps.com 11 Apr 2011 MDC_RBC-12/17-D48.A03 Page ...

Page 8

... Remote On/Off Control +INPUT The RBC may be turned off or on using the external remote on/off control. This terminal consists of a digital input to the internal PWM controller through a protective resistor and diode. The on/off input circuit should be CMOS logic referred to the –Input power COMMON terminal however TTL or TTL-LS logic will also work or a switch to ground ...

Page 9

... The descriptions contained herein do not imply the granting of licenses to make, use, or sell equipment constructed in accordance therewith. Specifi cations are subject to change without notice. www.murata-ps.com/locations RBC-12/17-D48 Series Quarter Brick, Regulated Bus Converters © 2011 Murata Power Solutions, Inc. email: sales@murata-ps.com 11 Apr 2011 MDC_RBC-12/17-D48.A03 Page ...