SU20K3/3XR5 Tripp Lite, SU20K3/3XR5 Datasheet

no-image

SU20K3/3XR5

Manufacturer Part Number
SU20K3/3XR5
Description
20kVA Tower Mount UPS Includes Five SURBC2030 Internal Battery Packs.
Manufacturer
Tripp Lite
Datasheet

Specifications of SU20K3/3XR5

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Model #: SU20K3/3XR5
SmartOnline 3-Phase UPS System - 3-Phase on-line, double-conversion protection for mission critical
applications
Description
Tripp Lite's SU20K3/3XR5 20kVA SmartOnline 3-Phase Intelligent, True On-Line Extended Runtime UPS System has been redesigned to save
valuable space and simplify runtime scalability. Power and battery components are combined into a single, small-footprint module (the smallest in its
class). A robust internal battery runtime capability can be easily extended by installing additional optional internal battery packs through the
convenient front panel access door. The SU20K3/3XR5 features a large internal battery compartment that contains more internal batteries than the
equivalent standard-run model (SU20K3/3) and more space to add additional optional internal battery packs to extend runtime.
The SU20K3/3XR5 provides mission-critical equipment with the highest level of power protection available. Large capacity 20,000VA/16,000 watt
UPS continually converts incoming AC power into filtered DC power, and then resynthesizes it back into AC power with a pure sine wave. Perfectly
regulated, continuous sine wave output with zero transfer time offers compatibility with all equipment types. IGBT inverter technology produces
output power with <3% THD (total harmonic distortion), allowing connected equipment to perform at its peak. A 3:1 crest factor safely supports a
variety of equipment, even those with wildly-fluctuating power demands. Extremely efficient operation saves money by lowering electricity
consumption. Hardwire input and output connections support a variety of permanent or PDU style power connections. SU20K3/3XR5 features
120/208V AC, 3-phase, 4-wire (plus ground), wye input and output. It also features a wide input voltage correction range: 96-144/166-250V AC.
Frequency is 50 or 60 Hz (auto-selectable). SU20K3/3XR5 includes internal power and battery components in a single small-footprint tower module.
Battery support can be extended with additional internal battery packs. A manual bypass switch as well as an automatic bypass function ensure
100% availability of connected equipment by safely passing through AC power when the UPS requires maintenance. Three built-in communication
ports (RS-232, contact closure and AS-400) work with included PowerAlert Software to simultaneously provide shutdown commands and reporting
on multiple servers without the need for costly accessories. An accessory slot accepts an optional internal SNMP card (model # SNMPWEBCARD)
for remote shutdowns, reboots and more. A Battery Start Switch allows cold restart of UPS during a prolonged blackout to utilize its batteries for
periodic system access or data retrieval. An Emergency Power Off button turns UPS output OFF and disables Bypass output. Built-in Emergency
Power Off (EPO) interface supports remote emergency shutdown in large facilities. Front panel combination LCD/LED display alerts users to a
variety of UPS operational modes and conditions. A
the reliability of the installation.
Package Includes
SU20K3/3XR5 UPS System (power and battery components in one module)
PowerAlert Software and cabling
1-year limited repair warranty
Highlights
20,000 VA (20kVA) EXTENDED RUNTIME tower UPS with internal batteries
Saves valuable space: power and battery components combined into a single
small-footprint module
Simplifies runtime scalability: convenient front panel battery access for
expandable runtime with additional internal battery packs
3-phase hardwire input and output (120/208VAC). Wide input voltage
correction range (96 - 144V AC / 166 - 250V AC)
IGBT technology and zero transfer time, on-line, double-conversion operation
3 communication ports, SNMP card slot and EPO jack
is included. A
start-up service program
E-mail:
Telephone: +(773) 869 1234
is recommended to enhance
Chicago, IL 60609 USA
saleshelp@tripplite.com
1111 West 35th Street
Tripp Lite

Related parts for SU20K3/3XR5

SU20K3/3XR5 Summary of contents

Page 1

... AC, 3-phase, 4-wire (plus ground), wye input and output. It also features a wide input voltage correction range: 96-144/166-250V AC. Frequency (auto-selectable). SU20K3/3XR5 includes internal power and battery components in a single small-footprint tower module. Battery support can be extended with additional internal battery packs. A manual bypass switch as well as an automatic bypass function ensure 100% availability of connected equipment by safely passing through AC power when the UPS requires maintenance ...

Page 2

... Extend runtime by installing optional internal battery packs (model # SURBC2030) through the front panel access door. SU20K3/3XR5 includes 5 internal battery packs and accepts 3 additional internal battery packs. A standalone battery module compartment with a 4 battery pack capacity and daisy-chain capability (model # SUBF2030) is available to further extend runtime ...

Page 3

Built-in UPS output Hardwire receptacles Output AC Sine wave waveform (AC mode) Output AC Pure Sine wave waveform (battery mode) INPUT Rated input current 60A (per phase, online) (at maximum load) Nominal Input 120V / 208V 3 phase wye Voltage(s) ...

Page 4

Undervoltage Maintains continuous operation without using battery power during brownout / undervoltage conditions 166 correction (3-Phase, 4-Wire, wye) LEDS ALARMS & SWITCHES LED Indicators 7 LED DISPLAY: AC input, bypass input, AC-DC charger, DC-AC inverter, AC output, ...

Page 5

UPS Shipping 59 44.4 dimensions (height x width x depth / inches) UPS Shipping 151 112.8 dimensions (height x width x depth / cm) Shipping weight 1133 (lbs) Shipping weight 510 (kg) UPS housing ...

Page 6

... UPS System (20k, 30k & 40k) - Premium Warranty Service Contracts - Includes primary battery cabinet plus one additional battery cabinet 3 Breaker Maintenance Bypass Panel for SU20K3/3, SU20K3/3XR5, SU20K3/3X and SU20KX UPS For remote monitoring and control via SNMP, Web, or Telnet. Monitors temperature, humidity and contact-closure inputs. (Requires SNMPWEBCARD or switched PDU ...

Related keywords