IEGH66-1-72-15.0-01-V AIRPAX, IEGH66-1-72-15.0-01-V Datasheet - Page 20

CIRCUIT BREAKER, HYD-MAG, 2P, 240V, 15A

IEGH66-1-72-15.0-01-V

Manufacturer Part Number
IEGH66-1-72-15.0-01-V
Description
CIRCUIT BREAKER, HYD-MAG, 2P, 240V, 15A
Manufacturer
AIRPAX
Series
IEGr
Datasheet

Specifications of IEGH66-1-72-15.0-01-V

Input Voltage Vac
240V
No. Of Poles
2
Current Rating
15A
Interrupting Capacity
7.5kA
Dielectric Strength
3.75kV
Trip Time
20s
Voltage Rating Vdc
80V
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
123
IAG / IUG / IEG / CEG DECISION TABLES
The ordering code for IAG/IUG/IEG/CEG/IDG circuit
protectors may be determined by following the decision
steps in the tables shown here.
The coding given permits a self-assigning part number
but with certain limitations. Special applications may
require a factory-assigned part number. Typical
examples are units with mixed ratings, combinations of
styles, or constructions not listed in the third decision
table. With these, it is suggested that order entry be by
description and/or drawings and a part number will be
established. Additionally, it is standard policy to
establish a factory-assigned part number whenever a
descriptive drawing exists to provide cross reference,
traceability and manufacturing control.
When specifying a circuit protector for AC motor start
or high inrush applications, the peak amplitude and
surge duration should be specified for factory
assistance in rating selection.
For example, the following is the code for a single pole,
IEG quick-connect type terminal, series unit with
auxiliary switch, designed for operation in a 50/60Hz
circuit. It has a short time delay, a rating of 20 amperes,
a black marked handle and is VDE approved.
To determine the ordering number for your particular
IAG/IUG/IEG/CEG unit, simply follow the steps shown.
You may use this number to place an order or as a
reference for further questions you may have.
Notes:
A. It is recommended that power leads be soldered to circuit
B. When “A” (metric thread mounting) is specified in the sixth
C. IEG, IEGH, IEGS, IEGHS, IEGX and IEGZX circuit protectors are
protectors having push-on type terminals for current trip
ratings above 20 amperes.
decision in combination with screw terminal option in the
second decision, metric screw terminals are supplied.
designed to meet 8mm creepage and clearance requirements
for installation Category III, Pollution Degree 3, Case A as
measured in IEC 664. Intended for use in equipment designed
to comply with IEC 601 and 950 and VDE 0804
and 0805.
IAG/IUG/IEG/CEG Series - Decision Tables
C = CCC Approved
This approval requires the addition of a C at the end
of the part number. The unit will not be VDE Approved.
IAG
IUG*
IEG**
CUG+
CEG++
IAGH
IUGH*
IEGH**
CUGH+
CEGH++
IDG***
IDGH***
IMG**
CMG++
IMGH**
CMGH++
*UL Recognized, CSA Certified
**UL Recognized, CSA Certified, VDE Approved
*** UL Recognized UL1500
+ UL489A Listed CSA Certified
++ UL489AListed CSA Certified VDE Approved
-0
-1
-1REC4
-1REC5
-1REG4
-1RS4
-1RLS4
-3
-4
1
Type
3
* Only one auxiliary switch is normally supplied on two or
three pole units. Switch is located in the right-hand pole
(viewed from terminal end) unless otherwise specified.
First Decision
Select Type and Terminal
Internal Configuration
Third Decision
Description
Switch only
Series
Series w/ auxiliary switch *
.110 quick connect
Series w/ auxiliary switch *
.187 quick connect
Series w/ auxiliary switch
(gold contacts)*
.110 quick connect
Series w/ alarm switch,
electrical trip,
.110 Q.C. terminals
Series w/ alarm switch,
electrical trip,
.110 Q.C. terminals (mid-trip only)
Shunt
Relay
One toggle handle per unit
One toggle handle per pole
One toggle handle per unit,
marine ignition protection
One toggle handle per pole
marine ignition protection
One toggle handle per unit
mid-trip indication
One toggle handle per pole
mid-trip indication
Note: Add "F" for flat screw terminals
* Not available on mid-trip units
** Available only on IAG, IUG units
S
X
ZX
BX
N
Handle and Mounting Options
Standard toggle/mounting,
no designation required
Toggle w/ snap-in mounting
Rocker w/ standard mounting*
ZX Rocker w/ integral mounting*
BX Rocker w/ integral mounting
Sealed toggle w/bushing mounting**
The shaded areas denote VDE approval options. This approval
requires the addition of a V at the end of the part number. The V will
be added to any part number formed entirely from shaded decisions.
If non-shaded areas are selected, the unit will not be VDE approved,
but other approvals still apply.
V = VDE Approved
Example:
IEG
http://airpax.sensata.com/
Push-on
Terminals
1
11
111
1111
*Not available in toggle seal handle type.
SW
-41
-42
-43
-49
-51
-52
-53
-59
-61
-62
-63
-64
-65
-66
-69
-71
-72
-73
-79
1
2
For addition of inertial delay, add an ìFî to any
delay numeral.
* CEG types are only available with DC ratings
4
Second Decision
Poles and Terminals
Fourth Decision
Frequency and Delay
Switch only
400Hz short delay
400Hz long delay
400Hz motor start
400Hz 150% instant trip
DC short delay*
DC long delay*
DC motor start*
DC 125% instant trip*
50/60Hz short delay
50/60Hz long delay
50/60Hz motor start
50/60Hz short delay
50/60Hz long delay
50/60Hz motor start
50/60Hz 125% instant trip
DC/60Hz short delay
DC/60Hz long delay
DC/60Hz motor start
DC/60 Hz 135% instant trip
2
1 - 1REC4 - 61 - 20.0 - 01 - V
Screw
Terminals
6
66
666
6666
3
Single pole
Two pole
Three pole
Four pole
4
5
7

Related parts for IEGH66-1-72-15.0-01-V