QOU215 SQUARE D, QOU215 Datasheet - Page 7

CIRCUIT BREAKER, THERMAL MAG, 2P, 15A

QOU215

Manufacturer Part Number
QOU215
Description
CIRCUIT BREAKER, THERMAL MAG, 2P, 15A
Manufacturer
SQUARE D
Series
QOUr
Type
Thermal/Magneticr
Datasheet

Specifications of QOU215

Actuator Style
Toggle
No. Of Poles
2
Current Rating
15A
Voltage Rating Vdc
48V
Voltage Rating Vac
240V
Mounting Type
DIN Rail
Actuator Type
Handle
Brand/series
QOU Miniture — Low Ampere
Number Of Poles
2
Special Features
Visi-Trip® Trip Indicator
Voltage Rating
120/240 V
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
09/2005
Interrupting Rating
The interrupting rating of a circuit breaker is the highest current at rated voltage that the circuit breaker
is intended to interrupt under standard test conditions. Circuit breakers must be chosen with
interrupting ratings equal to or greater than the maximum available short-circuit current at the point
where the circuit breaker is applied in the system (See Table 3).
Table 3:
1
Continuous Current Rating
The continuous current rating of a circuit breaker is defined by the National Electrical Manufacturers
Association (NEMA) as: “The maximum direct current or rms current, in amperes, at rated frequency
which a device or assembly will carry continuously without exceeding the specified limits of observable
temperature rise.” Sometimes referred to as the ampere rating or handle rating of the circuit breaker,
the continuous current rating relates to the system current flow under normal conditions.
UL Standard 489 states that circuit breakers must carry 100% of their continuous current rating
indefinitely (without tripping) at 104° F (40° C) in free air. QOU circuit breakers should be applied, per
the NEC, to carry 80% of their continuous current ratings in the intended enclosure. The continuous
current rating is indicated on the handle of each circuit breaker. See Table 1.
Switching Duty
The switching duty (SWD) listing applies only to 15 A and 20 A circuit breakers rated at 277 Vac or
less. The circuit breakers are subjected to specified temperature rise tests at predetermined periods
during the endurance operations.
NA = Not Applicable
DC ratings do not apply to circuit breakers rated for 10 A
Breaker
QOU-VH
Circuit
QOU-H
Type
QOU
Interrupting Rating
No. of
Poles
1
2
3
2
2
Ampere
Rating
80–100
80–125
80–100
10–30
10–70
10–70
10–70
15–30
15–60
QOU Miniature Circuit Breakers and Switches
120/240
10 kA
10 kA
10 kA
10 kA
22 kA
NA
NA
NA
NA
UL Listed Interrupting Rating—RMS Sym. Amperes
AC Volts
10 kA
10 kA
10 kA
240
NA
NA
NA
NA
NA
NA
© 2005 Schneider Electric All Rights Reserved
5 kA
277
NA
NA
NA
NA
NA
NA
NA
NA
Application Information
5 kA
5 kA
5 kA
5 kA
5 kA
NA
NA
NA
48
DC Volts
1
5 kA
5 kA
5 kA
60
NA
NA
NA
NA
NA
7