FUSE, ANTISURGE, 12.5A

S506-12-5-R

Manufacturer Part NumberS506-12-5-R
DescriptionFUSE, ANTISURGE, 12.5A
ManufacturerCooper/Bussmann
SeriesS506
S506-12-5-R datasheet
 


Specifications of S506-12-5-R

Voltage Rating Vac250VFuse Current12.5A
Breaking Capacity125A @ 250VACFuse Size Metric5mm X 20mm
SvhcNo SVHC (18-Jun-2010)Approval CategoryUL Recognised
Body Diameter5mmCartridgeRoHS Compliant
Blow CharacteristicTime DelayRohs CompliantYes
1
Page 1
2
Page 2
Page 1/2

Download datasheet (355Kb)Embed
Next
Description
• Time delay, low breaking capacity
• Optional axial leads available
• 5mm x 20mm physical size
• Glass tube, nickel-plated brass endcap construction
• Designed to IEC 60127-2 (32mA-10A)
S506 ELECTRICAL CHARACTERISTICS
2.1 In
2.75 In
4 In
In
max
min
max
min
32mA-100mA 2 min 200 ms 10 sec 40 ms
125mA-6.3A
2 min 600 ms 10 sec 150 ms 3 sec
8A-12.5A
2 min 600 ms 10 sec 150 ms 3 sec
Agency Information
• UL Recognized Card: (32mA-10A) Guide JDYX2,
File E19180
• CSA Component Acceptance: File 53787
• cURus Recognition: Guide JDYX8, File E19180
• Semko Approval, 32mA-10A
• VDE Approval, 32mA-10A
• BSI Approval, 32mA-10A
• IMQ Approval, 32mA-10A
• MITI Approval, 32mA-10A
Ordering
• Specify packaging, product, and option code
• For -R option, drop mA or A from product code
(i.e. S506-2-R)
Voltage
Interrupting Rating
Product Code
Rating
at Rated Voltage (50Hz)
AC
S506-32mA
250V
S506-40mA
250V
S506-50mA
250V
S506-63mA
250V
S506-80mA
250V
S506-100mA
250V
S506-125mA
250V
S506-160mA
250V
S506-200mA
250V
S506-250mA
250V
S506-315mA
250V
S506-400mA
250V
S506-500mA
250V
S506-630mA
250V
S506-800mA
250V
S506-1A
250V
S506-1.25A
250V
S506-1.6A
250V
S506-2A
250V
S506-2.5A
250V
S506-3.15A
250V
S506-4A
250V
S506-5A
250V
S506-6.3A
250V
S506-8A
250V
S506-10A
250V
S506-12.5A
250V
* DC Cold Resistance (Measured at <10% of rated current)
† Minimum Pre-Arching I
2
t (Measured at 10 In and rated voltage)
‡ Maximum Voltage Drop (Voltage drop was measured at 20°C ambient temperature at rated current)
OC-72
S506 Series, Time Delay, Glass Tube
RoHS
2002/95/EC
10 In
max
min
max
3 sec
10 ms 300 ms
20 ms 300 ms
Dimensions
20 ms 300 ms
Drawing Not to Scale
• Ratings above 6.3A have a 0.8mm diameter lead
SPECIFICATIONS
Typical DC
Cold Resistance
AC
(ohms)*
35A
21.7
35A
14.2
35A
9.5
35A
7.1
35A
4.5
35A
2.8
35A
2.0
35A
1.3
35A
1.0
35A
0.66
35A
0.46
35A
0.37
35A
0.268
35A
0.191
35A
0.131
35A
0.064
35A
0.046
35A
0.039
35A
0.029
35A
0.024
35A
0.018
40A
0.013
50A
0.010
63A
0.009
80A
0.007
100A
0.005
125A
0.004
5mm x 20mm Fuses
Minimum
Maximum
Pre-Arching I
2
t
Voltage
(A
2
Sec) AC†
Drop (mV)‡
0.0014
1050
0.0034
920
0.006
800
0.012
760
0.015
580
0.022
490
0.034
390
0.052
320
0.078
340
0.17
270
0.41
250
0.61
210
0.67
190
1.0
170
2.2
150
2.7
90
6.7
85
9.7
85
15
85
25
85
51
80
88
80
150
75
214
75
192
80
420
75
812
75

S506-12-5-R Summary of contents

  • Page 1

    ... DC Cold Resistance (Measured at <10% of rated current) † Minimum Pre-Arching (Measured and rated voltage) ‡ Maximum Voltage Drop (Voltage drop was measured at 20°C ambient temperature at rated current) OC-72 S506 Series, Time Delay, Glass Tube RoHS 2002/95/ max min max 3 sec ...

  • Page 2

    ... Cooper Electronic Technologies 1225 Broken Sound Parkway NW Suite F Boca Raton, FL 33487-3533 Tel: 1-561-998-4100 Fax: 1-561-241-6640 Toll Free: 1-888-414-2645 S506 Series, Time Delay, Glass Tube TIME CURRENT CURVE PACKAGING CODE OPTION CODE Cooper Bussmann Cooper Electronic Technologies P.O. Box 14460 Cooper (UK) Limited St ...