8020.0605.PT Schurter Inc, 8020.0605.PT Datasheet

no-image

8020.0605.PT

Manufacturer Part Number
8020.0605.PT
Description
FUSE, 6.3X32MM, P/TAIL, 20A
Manufacturer
Schurter Inc
Series
SUTr
Datasheet

Specifications of 8020.0605.PT

Voltage Rating Vac
250V
Fuse Current
20A
Breaking Capacity
500 A
Fuse Size Metric
6.3mm X 32mm
Svhc
No SVHC (15-Dec-2010)
Approval Bodies
CSA
Approval Category
UL Recognised
Case
RoHS Compliant
Fuse Size Code
3AG
Fuse Size Imperial
1/4 X 1.1/4"
Blow Characteristic
Slow Blow
Rohs Compliant
Yes
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Non resettable fuses
Description
- Up to 30 A, low resistance
- Ceramic Tube
Standards
- UL 248-14
- CSA C22.2 no. 248.14
Approvals
- UL File Number: E184831
Technical Data
Rated Voltage
Rated Current
Breaking Capacity
Characteristic
Admissible Ambient Air Temp. -40 °C to 85 °C
Climatic Category
Material: Tube
Material: Endcaps
Material: Axial Leads
Material: Filler
Unit Weight
Storage Conditions
Product Marking
Dimensions
Pre-Arcing Time
In = 12 A: ØA = 0.8 mm
In ≥ 15 A: ØA = 1.0 mm
Axial Lead Fuse, 6.3x32 mm, low resistance, up to 30 A
UL 248-14 · 250 V · Slow-Blow
Rated Current In
12 A - 30 A
40
.0 x In min.
4 h
.35 x In
250 V
12 - 30 A
500 A
Slow-Blow
40/085/21 acc. to IEC 60068-1
Ceramic
Nickel-Plated Brass
Tin-Plated Copper
Sand
3.9 g
0 °C to 60 °C, max. 70% r.h.
60 min
max.
32.8
, Type, Current, Voltage, Approvals
±1
2.0 x In min. 2.0 x In max.
5 s
40
60 s
32 mm
Applications
- Single-phase high current applications up to 30 A
- Industrial electronic
References
General Product Information
Packaging Details
Weblinks
Approvals, RoHS, CHINA-RoHS, Distributor-Stock-Check, Accessories,
Product Change Notification (PCN)
Soldering Methods
Solderability
Resistance to Soldering Heat
Fuses
SUT 6.3x32 Pigtail
www.schurter.com/pg0_2
Wave, Iron
235 °C / 2 sec acc. to IEC 60068-2-20,
Test Ta, method 1
260 °C / 5 sec acc. to IEC 60068-2-20,
Test Tb, method 1A


Related parts for 8020.0605.PT

8020.0605.PT Summary of contents

Page 1

... Non resettable fuses Axial Lead Fuse, 6.3x32 mm, low resistance 248-14 · 250 V · Slow-Blow Description - low resistance - Ceramic Tube Standards - UL 248-14 - CSA C22.2 no. 248.14 Approvals - UL File Number: E184831 Technical Data Rated Voltage 250 V Rated Current Breaking Capacity 500 A Characteristic Slow-Blow Admissible Ambient Air Temp. -40 ° °C Climatic Category 40/085/21 acc. to IEC 60068-1 Material: Tube ...

Page 2

... Multiple of Rated Current In 2 Cold Resi- Melting I²t 0.0 Order Number stance typ. Intyp. [A²s] [mV] [mΩ 8020.0603.PT 81 4.7 152 l 8020.0604.PT 87 3.6 750 8020.0605. 2.1 1010 l 8020.0606.PT 64 1.8 2050 l 8020.0607.PT 10 The specifications, descriptions and illustrations indicated in this document are based on Fuses current information. All content is subject to modifications and amendments. Non resettable fuses ...

Related keywords