48-DIN sized PID temperature controller with
adaptive fuzzy self-tuning
(1) All alarm types can be programmed to operate with or without ‘standby’ function
Fuzzy logic PID temperture
controller with 4-digit display
Relay output
Signal voltage for SSR
Current output
Analogue voltage 0-10VDC
Input type
Rated scale
Sensor resistance
Accuracy
Display
Control action
Proportional band
Integral time
Derivative time
Anti-reset windup
Reset range in PD action
Hysteresis in On/Off action
Proportional cycle
Output: relay types
Output: signal voltage types
Output: analogue types
Temperature alarm relay A1
Temperature alarm relay A2
Temp. alarms setting accuracy
Temperature alarms action
High limit alarm
Low limit alarm
High/low limits alarm
High/low limit range alarm
Absolute value (process) alarm
Absolute (process) reverse alarm
Sensor correction (input shift)
Sensor break protection
Supply voltage
Power consumption
Ambient temperature
Ambient humidity
Insulation resistance
Dielectric strength
Mounting
Front panel
Weight
Case material
Options and ordering codes
Specifications
User-selectable for K, J, R, B, PL-II and N
thermocouples and Pt100 resistance thermometers
User adjustable temperature scale to suit application
Two temperature alarm contacts independently
programmable with 12 functions
Alarm hysteresis adjustable from 0.1 to 100.0˚C or ˚F
3 levels of keypad security locking
Selectable operation: PID with adaptive fuzzy logic,
PID with auto-tune, PD or On/Off
Anti-reset windup (ARW) to reduce overshoot
Relay, voltage pulse, analogue 4-20mA or 0-10VDC
output
Very fast sampling period 0.125 seconds
Adjustable PV filter to slow down response if required
Wide 100-240 VAC or 24 VAC/DC supply voltage
IP54 protection
UL and CSA approved
(1)
(1)
FCS-13A
(2)
(2)
(1)
(1)
(1)
R
S
A
V
(1)
Fuzzy Logic Temperature
Controller with 4-Digit LED Display
–
–200 to 1370˚C –200 to 1000˚C
K-thermocouple
Optional extra: heater burnout alarm.
Please note: All models supplied with A2: Two alarms, BL: Screw
mounting bracket, IP: IP54 protection.
R
Power terminals, Control output terminals and Power terminals, Alarm output terminals and Power terminals,
/
Sensor input terminals and Control output terminals, Sensor input terminals and Alarm output terminals,
Control output terminals and ground, Alarm output terminals and ground, Sensor input terminals and
1 to 120 seconds, Relay output type: Factory set to 30 secs; Signal voltage type: Factory set to 3 secs
1.5k VAC for 1 min between: Sensor input terminals and ground, Power terminals and ground,
M
J-thermocouple
M
±0.3% of full scale ± 1 digit (Type B thermocouple 0-300˚C, 0-600˚F accuracy not specified)
4 to 20mA DC - max. load resistance 550Ω, 0-10VDC – output impedance 500Ω
100-240VAC supply
24VAC/DC supply
Multisensor input
100-240VAC
85 to 264VAC 50/60Hz (100-240 VAC+10%–15%); 20 to 28 VDC/AC 50/60Hz
ON/OFF action, hysteresis 0.1 to 100.0˚C (˚F), Factory set to 1.0˚C (˚F)
User-selectable: Fuzzy self-tuning PID, PID with autotune, PD, On/Off
Within the proportional band, providing within –199.9 to 999.9˚C (˚F)
(2) Do not apply voltage between sensor input terminals and control output terminals of FCS-13A-A, FCS-13A-S and FCS-13A-V models
SPNO: 250V, 3A resistive load; 250V, 1A inductive load, cos ø = 0.4
SPNO: 250V 3A resistive load; 250V, 1A inductive load, cos ø = 0.4
SPNO: 250V 3A resistive load; 250V, 1A inductive load, cos ø = 0.4
PV: 4-digit red LED, 8mm high; SV: 4-digit green LED, 8mm high
Light grey polycarbonate, flame retardant and self-extinguishing
R-thermocouple
Input range minimum value to input range maximum value
Input range minimum value to input range maximum value
0 to 1760˚C
1 to 3600 secs (off when set to 0), Factory set to 200 secs
1 to 3600 secs (off when set to 0), Factory set to 50 secs
12VDC +2VDC/–0VDC 40mA, short-circuit protected
Control output terminals and Alarm output terminals
–100.0 to 100.0˚C (˚F), Factory set to 0.0˚C (˚F)
100Ω or less
Deviation from SV: 1 to 200˚C (˚F)
Deviation from SV: 1 to 200˚C (˚F)
0.1 to 100.0%, Factory set to 2.5%
Membrane sheet keyboard, IP54
Deviation from SV: ±200˚C (˚F)
Deviation from SV: ±200˚C (˚F)
35 to 85% r.h. (non-condensing)
B-thermocouple
Upscale: Control output off
0 to 1820˚C
±0.3% of full scale ±1 digit
Automatic in PID modes
>10MΩ at 500VDC
0.1 to 100.0˚C (˚F)
140g approx
8VA approx.
0 to 50˚C
Flush
PL-II thermocouple N-thermocouple
0 to 1390˚C
AND ORDERING
AND ORDERING
INFORMATION
INFORMATION
0 to 1300˚C
PRICE
PRICE
–199.9 to 850.0˚C –199.9 to 500.0˚C
DIN Pt100 RTD
FCS-13A
10Ω per wire or less
Guarantee
Year
3
J Pt100 RTD