212459 Megger, 212459 Datasheet

no-image

212459

Manufacturer Part Number
212459
Description
Battery Analog Major Megger Insulation Tester
Manufacturer
Megger
Datasheet

Specifications of 212459

100, 250, 500 & 1000 V
2 GOhms
Resistance
2000 Ohms
Current Rating
2 mA
Frequency
60 Hz
Measured Components
Voltages
Safety Rating
2.5 % of Full Scale
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Major Megger
Insulation Resistance Testers
DESCRIPTION
Quality is crafted into every Major MEGGER® Insulation
Tester, with excellent test voltage regulation, direct
measurement readout and an external guard terminal to
eliminate surface leakage current from the measurement.
Five models are available for general purpose testing which
include a low-voltage model.
All are portable, self-contained instruments designed to give
rapid and accurate measurements.
Four of the models feature an analog display having four
selectable test voltages of 100, 250, 500 and 1000 Vdc,
measuring insulation resistance up to 2000 MΩ, and an ohm
range to 5000 ≈ . The other model has four test voltages of
50, 100, 250 and 500 Vdc measuring insulation resistance up
to 1000 M≈ .
The only other difference between the five analog models is
the type of power source. Power for models MJ159 and
MJ160 is derived from a low-voltage, hand cranked
generator which has been designed to be easy to turn even
under full load conditions. The low-voltage generator is
connected to an electronic inverter to provide a very stable
test voltage. Accuracy of measurement is unaffected by
variations in the generator cranking speed and the test
voltage is maintained at its rated value. Power for model
MJ359 is provided by 120 V ac 50/60 Hz or low-voltage
generator. Model MJ559 is also 120 Vac 50/60 Hz or internal
rechargeable batteries and model MJ459 is powered by 6
replaceable “AA” alkaline cells.
I
I
I
As a safety feature, the ac voltage range becomes effective as
soon as the instrument is connected to the circuit under
test. Therefore, a warning is given that the circuit under test
is not de-energized before the instrument is operated.
Though calibrated for ac voltage, this range also monitors
the automatic discharge feature so that after equipment
having capacitance (i.e. a cable), has been tested, an
indication can be given that the voltage has discharged to a
level that is safe for removing the test leads.
Each instrument has a guard terminal which may be used to
prevent the effects of surface leakage from influencing the
readings. This is achieved by diverting the leakage current
through the guard terminal and away from the instrument’s
measuring circuit.
Each instrument is built into a strong ABS plastic case with a
fold down carrying handle.
APPLICATIONS
The Major Meggers have been designed for convenience
and ease-of-use when testing complex or larger electrical
installations, and commissioning, servicing or maintaining
electrical equipment. They are designed for the safe testing
of motors, generators. cables, switchgear, transformers,
distribution networks, industrial and domestic installations,
components and appliances.
The range of insulation test voltages available allows one
instrument to be used for a variety of applications. For
example, installations and equipment can be tested at
No scale multipliers
Multiple test voltages for spot and step
voltage testing
Guard terminal to eliminate surface
leakage current
Insulation Resistance Testers
MJ TESTERS

Related parts for 212459

212459 Summary of contents

Page 1

... Each instrument is built into a strong ABS plastic case with a fold down carrying handle. APPLICATIONS The Major Meggers have been designed for convenience and ease-of-use when testing complex or larger electrical installations, and commissioning, servicing or maintaining electrical equipment. They are designed for the safe testing of motors, generators ...

Page 2

V d.c. when this requirement is specified, also aircraft and tele-communications equipment can be tested at the relatively low 100 V d.c. and 110 V to 120 V a.c. systems can be tested using 250 V d.c. Test leads ...

Page 3

... Cat. No. Item 212159 Optional Accessories 212359 Test record card (pack of 20) 212459 Black test lead with large alligator clip 212559 Red test lead with large alligator clip Green test lead with large alligator clip 212160 Set of test leads with fused prods (FPK5) - 1000 V a ...

Related keywords