TWINSPOTNM ETERNA, TWINSPOTNM Datasheet

EMERGENCY LIGHT, TWIN SPOT, 2X20W

TWINSPOTNM

Manufacturer Part Number
TWINSPOTNM
Description
EMERGENCY LIGHT, TWIN SPOT, 2X20W
Manufacturer
ETERNA
Datasheet

Specifications of TWINSPOTNM

Length
310mm
Width
310mm
Depth
70mm
Ip/nema Rating
IP20
Svhc
No SVHC (15-Dec-2010)
Base Type
12V 20W BA 15S
External Depth
70mm
External Length / Height
310mm
External Width
310mm
Height
310mm
Lamp Base Type
12V
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lamp replacement:
>
>
>
>
>
>
Replacement lamp type:
Type:
Replacement battery type:
12V 7Ah Lead / Acid
Cleaning:
>
>
Eventually, you may want to replace this light fitting:
When your light fitting and or battery pack come to the end of their life or you choose to update
or upgrade the fitting by replacing it, please do not dispose of it with your normal household
waste, please recycle where facilities exist. When you need to dispose of this fitting, check with
your retailer or local authority for suitable options. New regulations will encourage the recycling
of Waste from Electrical and Electronic Equipment ( European “WEEE Directive” effective
August 2005 ).
If you experience problems:
If your light is defective or develops a fault, please return it to the place where you bought it. You can call our
Helpline for advice. The Helpline will gladly give advice on any aspect of any Eterna Lighting product but may not be
able to give specific instructions regarding individual installations.
If in doubt, consult a qualified electrician.
Help line:
Tel: 01933 673 144
For answers to frequently asked questions ( FAQs ) and other information visit our web-site
www.eterna-lighting.co.uk
Switch off the electricity at the mains.
Remove two screws on the front of the light and lift
off the diffuser.
Remove the bayonet lamp.
Insert new lamp.
Replace diffuser.
Restore the power and perform operation check.
Clean this light fitting only with a soft dry cloth
Do not use any chemical or abrasive cleaners.
12V 20 W
BA 15s
Fax: 01933 678 083
Email: sales@eterna-lighting.co.uk
Battery replacement:
If after routine operation check, the lamp does not remain
lit for the three hour period, new batteries may be
required.
1)
2)
3)
4)
5)
6)
7)
8)
9)
10) Close and secure the front cover.
11) Restore power and allow to charge for 24 hours.
12) Perform full operation check and update test record.
Switch off the electricity at the mains.
Allow batteries to fully discharge then reconnect to
supply and allow to charge for 24 hours.
Test again for 3 hours, if light does not remain lit
change the battery pack as follows:
Remove the two screws on each side of the front
panel and lift off.
Unplug the battery leads from the batteries.
Lift the batteries out of the case.
Write current date on the new batteries.
Fit new batteries into the case.
Reconnect the battery leads.
Specification:
Non-maintained emergency light
Power
Continuous illumination
Battery
Recharge time
Over-discharge protection
PLEASE READ THESE INSTRUCTIONS BEFORE
PLEASE RETAIN FOR FUTURE REFERENCE
INSTALLING YOUR NEW FITTING
TWINSPOTNM
2×20W
Model(s)
- -
~24 hours
12V 7Ah
>3 hours
2 × 20W
Yes

Related parts for TWINSPOTNM

TWINSPOTNM Summary of contents

Page 1

... Tel: 01933 673 144 Fax: 01933 678 083 Email: sales@eterna-lighting.co.uk For answers to frequently asked questions ( FAQs ) and other information visit our web-site www.eterna-lighting.co.uk Non-maintained emergency light 2×20W Model(s) TWINSPOTNM Specification: Power 2 × 20W Continuous illumination >3 hours Battery 12V 7Ah Recharge time ...

Page 2

Read this first: Installation: > 1) Undo the screws on each side of the front panel and This light fitting must be installed in accordance lift off. with the Building Regulations making reference 2) Disconnect and remove the batteries noting ...

Related keywords