HS19F1B SOLA HEVI DUTY, HS19F1B Datasheet
HS19F1B
Specifications of HS19F1B
Related parts for HS19F1B
HS19F1B Summary of contents
Page 1
... Now only the secondary windings are transforming voltage and current. The majority of the KVA load passes directly from the supply to the load. This is why buck-boost transformers can supply a load with a much larger KVA rating than the nameplate indicates. Applications ...
Page 2
... For determining the correct size of breaker or fuse for a given range of input or output ampere ratings, refer to Section 450-4, of the National Electric Code (NEC). "450-4, Autotransformers 600 Volts, Nominal or Less. (a) Overcurrent Protection. Each autotransformer 600 volts, nominal or less shall be protected by an individual overcurrent device installed in series with each ungrounded input conductor ...
Page 3
... HS19B100 0.15 12.5 HS19B150 0.25 20.8 HS19B250 0.5 41.6 HS19F500B 0.75 62.5 HS19F750B 1 83.3 HS19F1B 1.5 125 HS19F1.5A 2 166.6 HS19F2A 3 250 HS19F3A 5 416.5 HS19F5A 7.5 625 HS19F7.5A Group 2 – 120 x 240 Volt Primary, 16/32 Volt Secondary Maximum Secondary Amperage ...
Page 4
... Connect Interconnect Voltage Lines To 240 & 120 H1 & Secondary Connect Interconnect Voltage Lines & 12-0-12 X1-X2- & HS19 and S19 Series 216 Buck–Boost Transformers Height Width (inch) (inch Non-Encapsulated - 50/60 Hz, Single Phase 3. 5 Encapsulated - 60 Hz, Single Phase 62.5 ...