2420-31-G-T Bourns Inc., 2420-31-G-T Datasheet

no-image

2420-31-G-T

Manufacturer Part Number
2420-31-G-T
Description
Manufacturer
Bourns Inc.
Datasheet

Specifications of 2420-31-G-T

Lead Free Status / RoHS Status
Not Compliant
The Bourns
patented Switch-Grade Fail-Short mechanism to provide robust and reliable surge and thermal overload protection at a very
competitive price. The 2420 Series is based on Bourns’ three-terminal common chamber GDT. This design provides greatly
improved and balanced turn-on characteristics for overvoltage protection. The GDT is UL approved for use without a back-up
device. Air back-up devices can become contaminated; the circuitry of the 2420 eliminates this possibility. Our unique Switch-
Grade Fail-Short device provides more reliable thermal overload protection compared to commonly used solder pellet or insulation
burn-through designs.
Bourns
VDSL2 and high-speed Ethernet. The 2420 Series is an economical, reliable and low capacitance choice for overvoltage protection
of copper pair circuits.
DC Breakdown ............................................................................................................................................... 280-420 V
AC Breakdown @ 60 Hz ................................................................................................................................. 280-420 V
Impulse Breakdown
Insulation Resistance @ 100 Vdc ................................................................................................................... >1 GΩ
Insertion Loss @ 100 MHz .............................................................................................................................. Exceeds Category 5
Return Loss @ 100 MHz ................................................................................................................................. Exceeds Category 5
Capacitance Tip to Ring @ 1 MHz ................................................................................................................. <1.25 pF typical
Capacitance Tip or Ring to Ground @ 1 MHz ................................................................................................ <2.50 pF typical
Impulse Reset
Impulse Life Characteristics (Tip and Ring to Ground Simultaneously)
AC Life Characteristics (Tip and Ring to Ground Simultaneously)
High Current Capability and Thermal Operation (Tip and Ring to Ground) .................................................... >30 A rms, 15 min.
Storage and Operating Temperature .............................................................................................................. -55 to +85 °C
Telcordia analyzed for controlled (non-sealed) and uncontrolled, high-exposure (sealed) environments per GR 974 and SBC SR 5165.
Telcordia Technical Analysis Report DA-1597.
Notes:
1
2
Line to Line voltage is approximately 1.8 to 2 times the stated Line to Ground breakdown voltage.
Specifi cations are subject to change without notice.
Customers should verify actual device performance in their specifi c applications
Test Methods per UL 497, CSA C22.2, Telcordia GR 974, 1361 and SBC SR 5165.
Network applied
Per RUS PE-80
Characteristics
100 V/µs .................................................................................................................................................... 625 V
1000 V/µs .................................................................................................................................................. 875 V
52 V, 260 mA ............................................................................................................................................. <10 ms
135 V, 200 mA ........................................................................................................................................... <10 ms
150 V, 200 mA ........................................................................................................................................... <150 ms
10 A, 10/1000 µs ....................................................................................................................................... >3000 operations
100 A, 10/1000 µs ..................................................................................................................................... >300 operations
300 A, 10/1000 µs ..................................................................................................................................... >100 operations
500 A, 10/1000 µs ..................................................................................................................................... >400 operations
2,000 A, 10/250 µs .................................................................................................................................... >25 operations
5,000 A, 20/100 µs .................................................................................................................................... >2 operations
20,000 A, 8/20 µs ...................................................................................................................................... >1 operation
0.5 A rms continuous ................................................................................................................................ >30 seconds
1 A rms, 1 second, 600 ft. cable ............................................................................................................... >60 operations
1 A rms, 1 second, 1 mile cable ................................................................................................................ >60 operations
10 A rms, 1 second ................................................................................................................................... >5 operations
65 A rms, 11 cycles ................................................................................................................................... >1 operation
120 A rms, 0.1 second .............................................................................................................................. 1 operation
®
2420 Series 5-Pin protectors can be used universally for broadband voice and data circuits including ADSL, ADSL2+,VDSL,
®
3-type 2420 overvoltage protection modules utilize Bourns’ proprietary high-effi ciency gas discharge tube with our
1
2420 Series - 5-Pin Gas Discharge Tube (GDT) Protector
Features
Superior protection at a low price
Balanced TRIGARD
Patented Switch-Grade Fail-Short Device
Quick response and high energy handling
Low capacitance (<2.5 pF) - ideal for high-
speed networks in high exposure
environments
®
Meets test requirements of Telcordia
GR 974, GR1361, SBC SR 5165 and
RUS PE-80
Solid brass, gold-plated pins
Test point access option
Sealed option for harsh environments
C
U L
®
US LISTED
per UL 497 (File: 53117)
2
2

Related parts for 2420-31-G-T

2420-31-G-T Summary of contents

Page 1

... Bourns 2420 Series 5-Pin protectors can be used universally for broadband voice and data circuits including ADSL, ADSL2+,VDSL, VDSL2 and high-speed Ethernet. The 2420 Series is an economical, reliable and low capacitance choice for overvoltage protection of copper pair circuits. Characteristics Test Methods per UL 497, CSA C22.2, Telcordia GR 974, 1361 and SBC SR 5165. ...

Page 2

... DIA. 2 PLCS. (.085) 19.0 (0.75) 11.2 (0.44) 3.6 (0.14) MM DIMENSIONS: (INCHES Yellow/Standard 3C1E = 2420-31-G-T (black, with test points) 3C3E = 2420-33-G-T (red, with test points) 2420-3 MODULE 42.17 (1.66) 29.9 (1.18) 5.1 (0.20) 10.2 (0.40) 2420-7 MODULE 30.99 (1.22) 24.9 (0 ...

Related keywords