24338 SQUARE D, 24338 Datasheet

no-image

24338

Manufacturer Part Number
24338
Description
MINIATURE CIRCUIT BREAKER 240/415V 20A
Manufacturer
SQUARE D
Datasheet
Product data sheet
Characteristics
Complementary
Environment
Mar 31, 2012
[In] rated current
[Ue] rated operational voltage
Magnetic tripping limit
Breaking capacity
[Ics] rated service breaking capacity
[Ui] rated insulation voltage
[Uimp] rated impulse withstand voltage
Contact position indicator
Control type
Local signalling
Mounting mode
Mounting support
9 mm pitches
Product weight
Mechanical durability
Connections - terminals
Tightening torque
Standards
Tropicalisation
Relative humidity
Operating altitude
Ambient air temperature for operation
Ambient air temperature for storage
RoHS EUR conformity date
RoHS EUR status
24338
miniature circuit breaker - C60N - 2 poles - 20
A - C curve
Main
Circuit breaker applica-
tion
Range of product
Device short name
Poles description
Number of protected
poles
Neutral position
Network type
Trip unit technology
Curve code
Suitability for isolation
20 A ( 30 °C )
440 V AC
440 V AC
5...10 x In
Icn 6 kA at 400 V AC conforming to IEC 60898
Icu 20 kA at 230...240 V AC conforming to IEC 60947-2
Icu 10 kA at 400...415 V AC conforming to IEC 60947-2
Icu 6 kA at 440 V AC conforming to IEC 60947-2
Icu 20 kA at 125 V DC conforming to IEC 60947-2
Ics 4.5 kA 440 V AC conforming to IEC 60947-2
Ics 6 kA 400 V AC conforming to IEC 60898
Ics 7.5 kA 400...415 V AC conforming to IEC 60947-2
Ics 15 kA 230...240 V AC conforming to IEC 60947-2
500 V AC conforming to IEC 60947-2
6 kV conforming to IEC 60947-2
Yes
Operating handle
Positive break indication
Fixed
35 mm symmetrical DIN rail
4
0.24 kg
20000 cycles
Tunnel type terminals 16 mm² flexible
Tunnel type terminals 25 mm² rigid
2 N.m
IEC 60898
IEC 60947-2
2 conforming to IEC 60068-1
95 % ( 55 °C )
2000 m
-25...60 °C
-40...70 °C
0643
Compliant
Distribution
C60
C60N
2P
1
Left
AC
Thermal-magnetic
C
Yes conforming to IEC 60947-2
1

Related parts for 24338