ATV61HC50Y SQUARE D, ATV61HC50Y Datasheet

no-image

ATV61HC50Y

Manufacturer Part Number
ATV61HC50Y
Description
ALTIVAR 61 DRIVE 550 HP 575/690 VOLT
Manufacturer
SQUARE D
Datasheet
Product data sheet
Characteristics
Apr 1, 2012
ATV61HC50Y
variable speed drive ATV61 - 500kW / 690V -
550HP / 575V - IP20
Main
Range of product
Product or component
type
Product specific appli-
cation
Component name
Motor power kW
Motor power hp
Power supply voltage
Supply number of
phases
Line current
EMC filter
Assembly style
Maximum prospective
line Isc
Maximum transient cur-
rent
Nominal switching fre-
quency
Switching frequency
Asynchronous motor
control
Synchronous motor
control profile
Communication port
protocol
Type of polarization
Option card
Altivar 61
Variable speed drive
Pumping and ventilation machine
ATV61
400 kW 3 phases at 500 V
500 kW 3 phases at 690 V
550 hp 3 phases at 575 V
500...690 V (- 15...10 %)
3 phases
494 A for 600 V 3 phases 400 kW / 550 hp
505 A for 690 V 3 phases 400 kW / 550 hp
547 A for 500 V 3 phases 400 kW / 550 hp
Level 3 EMC filter
With heat sink
35 kA 3 phases
708 A for 60 s 3 phases
2.5 kHz
2.5...4.9 kHz adjustable
2.5...4.9 kHz with derating factor
Voltage/Frequency ratio, 2 points
Voltage/Frequency ratio, 5 points
Flux vector control without sensor, standard
Voltage/Frequency ratio - Energy Saving, quadratic
U/f
Vector control without sensor, standard
CANopen
Modbus
No impedance for Modbus
APOGEE FLN communication card
BACnet communication card
CC-Link communication card
Controller inside programmable card
DeviceNet communication card
Ethernet/IP communication card
Fipio communication card
I/O extension card
Interbus-S communication card
LonWorks communication card
METASYS N2 communication card
Modbus Plus communication card
Modbus TCP communication card
Modbus/Uni-Telway communication card
Multi-pump card
Profibus DP communication card
Profibus DP V1 communication card
1

Related parts for ATV61HC50Y

ATV61HC50Y Summary of contents

Page 1

... Product data sheet Characteristics Apr 1, 2012 ATV61HC50Y variable speed drive ATV61 - 500kW / 690V - 550HP / 575V - IP20 Main Range of product Altivar 61 Product or component Variable speed drive type Product specific appli- Pumping and ventilation machine cation Component name ATV61 Motor power kW 400 kW 3 phases at 500 V ...

Page 2

Complementary Product destination Power supply voltage limits Power supply frequency Power supply frequency limits Continuous output current Speed drive output frequency Speed range Speed accuracy Torque accuracy Transient overtorque Braking torque Regulation loop Motor slip compensation Diagnostic Output voltage Electrical ...

Page 3

Discrete output number Discrete output type Maximum response time Minimum switching current Maximum switching current Discrete input number Discrete input type Discrete input logic Acceleration and deceleration ramps Braking to standstill Protection type Insulation resistance Frequency resolution Type of connector ...

Page 4

Environment Noise level Dielectric strength Electromagnetic compatibility Standards Product certifications Pollution degree Degree of proctection Vibration resistance Shock resistance Relative humidity Ambient air temperature for operation Ambient air temperature for storage Operating altitude RoHS EUR status RoHS EUR conformity date ...

Page 5

... Option cards: I/O extension cards, communication cards or "Controller Inside” programmable card. Dimensions with 2 Option Cards (1) Dimensions 1120 392 532.5 Dimensions in in 44.09 15.43 20.96 (1) Option cards: I/O extension cards, communication cards or "Controller Inside” programmable card. ATV61HC50Y 495 1120 2.95 19.49 44. ...

Page 6

... To ensure proper air circulation in the drive: ● Fit ventilation grilles. ● Ensure that there is sufficient ventilation. If there is not, install a forced ventilation unit with a filter. The openings and/or fans must provide a flow rate at least equal to that of the drive fans (refer to the product characteristics). 6 ATV61HC50Y X1 in in. 9. in. 15.75 ...

Page 7

Use special filters with IP 54 protection. ● Remove the blanking cover from the top of the drive. Dust and Damp Proof Metal Enclosure (IP 54) The drive must be mounted in a dust and damp proof enclosure in ...

Page 8

... VA transformer 220 V secondary (1) Line choke (three-phase); mandatory for ATV61HC11Y…HC80Y drives (except when a special transformer is used (12-pulse)). (2) For ATV61HC50N4, ATV61HC63N4 and ATV61HC50Y…HC80Y drives, refer to the power terminal connections diagram. (3) Fault relay contacts. Used for remote signalling of the drive status. (4) Connection of the common for the logic inputs depends on the positioning of the SW1 switch. The above diagram shows the internal power supply switched to the “ ...

Page 9

... Switch disconnector (Vario) (1) Line choke (three-phase), mandatory for ATV61HC11Y…HC80Y drives (except when a special transformer is used (12-pulse)). (2) For ATV61HC50N4, ATV61HC63N4 and ATV61HC50Y…HC80Y drives, refer to the power terminal connections diagram. (3) Fault relay contacts. Used for remote signalling of the drive status. (4) Connection of the common for the logic inputs depends on the positioning of the SW1 switch. The above diagram shows the internal power supply switched to the “ ...

Page 10

... Line choke (three-phase), mandatory for and ATV61HC11Y…HC80Y drives (except when a special transformer is used (12-pulse)). (5) The logic output can be used to signal that the machine safe stop state. (6) For ATV61HC50N4, ATV61HC63N4 and ATV61HC50Y…HC80Y drives, refer to the power terminal connections diagram. (7) Fault relay contacts. Used for remote signalling of the drive status. (8) Connection of the common for the logic inputs depends on the positioning of the SW1 switch. The above diagram shows the internal power supply switched to the “ ...

Page 11

... For stopping times requiring more than 30 seconds in category 1, use a Preventa XPS AV safety module which can provide a maximum time delay of 300 seconds. (7) For ATV61HC50N4, ATV61HC63N4 and ATV61HC50Y…HC80Y drives, refer to the power terminal connections diagram. (8) Fault relay contacts. Used for remote signalling of the drive status. ...

Page 12

... Product data sheet Performance Curves Derating Curves The derating curves for the drive nominal current (In) depend on the temperature and the switching frequency. For intermediate temperatures (e.g. 55°C), interpolate between 2 curves. X Switching frequency 12 ATV61HC50Y ...

Related keywords