H3DK-HCL AC100-120V Omron, H3DK-HCL AC100-120V Datasheet - Page 27

no-image

H3DK-HCL AC100-120V

Manufacturer Part Number
H3DK-HCL AC100-120V
Description
TIMER, POWER OFF DELAY, 120S, 110AC
Manufacturer
Omron
Datasheet

Specifications of H3DK-HCL AC100-120V

Contact Configuration
SPDT
Delay Time Range
1s To 120s
Adjustment Type
Screwdriver Slot
Relay Mounting
DIN Rail
Svhc
No SVHC (15-Dec-2010)
Contact Current Ac Max
5A
Contact Current Dc
RoHS Compliant
● Wiring
The H3DK-H acts like a high-impedance circuit. Therefore, the
Timer may not reset if it is influenced by inductive voltage. To
eliminate inductive voltage, the wires connected to the Timer
must be as short as possible and should not be installed parallel
to power lines. If the Timer is influenced by inductive voltage that
is 30% or more of the rated voltage, connect a CR filter with a
capacitance of approximately 0.1 µF and a resistance of approx-
imately 120 Ω or a bleeder resistor between the power supply
terminals.
If there is any residual voltage due to current leakage, connect a
bleeder resistor between the power supply terminals.
● Operating Frequency
● DC Power Consumptions (Reference Information)
● Other Precautions
• The H3DK-H may malfunction if it is used as shown below. Do
• If the Timer is mounted on a control panel, dismount the Timer
• Refer to the datasheet for the H3DK for cable selection and
• The power supply terminals and input terminals are not iso-
• If double or reinforced insulation is required, use the double or
H3DK-M2/-S2
H3DK-M1/-S1
H3DK-F
H3DK-G
H3DK-HBS/-HBL
not use the H3DK-H in these ways.
Timer Repeatedly Times Out in Cycles of 3 s or Less
In the above case, use the H3DK-M2/-M1 in D mode (signal
OFF delay).
from the control panel before carrying out a voltage withstand
test between the electric circuits and non-current-carrying
other conditions for compliance with EMC standards.
lated. There is basic insulation between the power supply ter-
minals and output terminals.
reinforced insulation defined in IEC 60664 that is suitable for
the maximum applied voltage for the clearance, solid insula-
tion, and other factors.
Output
Power
EN/IEC Standard Compliance
At 24 VDC: 1.2 W max.
At 24 VDC: 1.1 W max.
At 24 VDC: 1.1 W max.
At 24 VDC: 1.2 W max.
At 24 VDC: 1.2 W max.
or less
3 s
or less
3 s
Notice to Users of the H3DK in the USA and Canada
Please use the following installation information instead of the
general information in this document in order to use the product
under certified conditions of UL and CSA when the product is
installed in the USA or Canada. These conditions are required by
NFPA 70, National Electrical Code in the USA and the Canadian
Electrical Code, Part I in Canada and may vary from information
given in this document.
• The H3DK-H uses a latching relay for the output. Shock, such
• The life expectancy of the control output contacts is greatly
• If the power supply voltage is gradually increased, a power
• Make sure that residual voltage or inductive voltage is not
• Error in the operation time of the Timer is given as a percent-
• When switching a microload, check the specified minimum
• When setting the operating time, do not turn the dial beyond
• If better accuracy is required in the set time, adjust the dial
• If the Timer is reset immediately after timing out, make sure
• When directly switching a DC load, the switching capacity will
• Use an isolated source for power input for the H3DK-@A.
• Environment
• Power Supply: The inputs are non-isolated (applicable to
• Pollution Degree
Precautions for Compliance with UL Standards
metal parts of the Timer. (Otherwise, the internal circuits of the
Timer may be damaged.)
as dropping the H3DK-H during shipment or handling, can
cause the output contacts to reverse to the neutral position.
Check the output status with a tester before using the H3DK-
H.
affected by switching conditions. Always confirm operation
using the actual conditions and equipment before using the
Timer and make sure that the number of switching operations
presents no problems in performance. If Timer application is
continued after performance has deteriorated, insulation fail-
ure between circuits, burning of the control output relay, or
other problem will eventually occur.
reset may occur or the Timer may time out. Use a switch,
relay, or other device with contacts to apply the power supply
voltage all at once.
applied after the power turns OFF.
age of the full-scale time. The absolute value of the error will
not change even if the set time is changed. Therefore, always
use the Timer with the set time set as close as possible to the
full-scale value of the set time range.
load given for the Timer model you are using.
the scale range.
while measuring the operation time.
that the circuit configuration allows sufficient resetting time.
Errors will occur in the sequence if there is not sufficient reset-
ting time.
be lower than when switching an AC load.
Use an isolated source with external overcurrent protection of
16 A maximum for the source and input. (The input is applica-
ble to the H3DK-M only.)
Surrounding Air Temperature: 55°C
H3DK-M only).
The same power supply as the main power source must be
used for that for input.
Pollution degree II
and CSA Standards
H3DK
27