Characteristics
Apr 1, 2012
LC1D186F7
TeSys D contactor - 3P(3 NO) - AC-3 - <= 440
V 18 A - 110 V AC coil
Main
Range of product
TeSys D
Product or component
Contactor
type
Device short name
LC1D
Contactor application
Motor control
Resistive load
Utilisation category
AC-1
AC-3
Poles description
3P
Power pole contact
3 NO
composition
[Ue] rated operational
<= 690 V DC for power circuit
voltage
<= 690 V AC 25...400 Hz for power circuit
[Ie] rated operational
18 A (<= 60 °C) at <= 440 V AC AC-3 for power cir-
current
cuit
32 A (<= 60 °C) at <= 440 V AC AC-1 for power cir-
cuit
Motor power kW
10 kW at 660...690 V AC 50/60 Hz
10 kW at 500 V AC 50/60 Hz
9 kW at 415...440 V AC 50/60 Hz
7.5 kW at 380...400 V AC 50/60 Hz
4 kW at 220...230 V AC 50/60 Hz
Motor power HP (UL /
15 hp at 575/600 V AC 50/60 Hz for 3 phases mo-
CSA)
tors
10 hp at 460/480 V AC 50/60 Hz for 3 phases mo-
tors
5 hp at 230/240 V AC 50/60 Hz for 3 phases motors
5 hp at 200/208 V AC 50/60 Hz for 3 phases motors
3 hp at 230/240 V AC 50/60 Hz for 1 phase motors
1 hp at 115 V AC 50/60 Hz for 1 phase motors
Control circuit type
AC 50/60 Hz
Control circuit voltage
110 V AC 50/60 Hz
Auxiliary contact com-
1 NO + 1 NC
position
[Uimp] rated impulse
6 kV conforming to IEC 60947
withstand voltage
Overvoltage category
III
[Ith] conventional free
32 A at <= 60 °C for power circuit
air thermal current
10 A at <= 60 °C for signalling circuit
Irms rated making ca-
300 A at 440 V for power circuit conforming to IEC
pacity
60947
250 A DC for signalling circuit conforming to IEC
60947-5-1
140 A AC for signalling circuit conforming to IEC
60947-5-1
Rated breaking capac-
300 A at 440 V for power circuit conforming to IEC
ity
60947
[Icw] rated short-time
84 A <= 40 °C 1 min power circuit
withstand current
40 A <= 40 °C 10 min power circuit
240 A <= 40 °C 1 s power circuit
145 A <= 40 °C 10 s power circuit
140 A 100 ms signalling circuit
120 A 500 ms signalling circuit
100 A 1 s signalling circuit
1

LC1D186F7 Summary of contents

  • Page 1

    ... Product data sheet Characteristics Apr 1, 2012 LC1D186F7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 110 V AC coil Main Range of product TeSys D Product or component Contactor type Device short name LC1D Contactor application Motor control Resistive load Utilisation category AC-1 AC-3 Poles description 3P Power pole contact ...

  • Page 2

    Complementary Coil technology Control circuit voltage limits Inrush power in VA Hold-in power consumption in VA Heat dissipation Auxiliary contacts type 2 Associated fuse rating <= 690 V coordination type 2 for power circuit 50 A ...

  • Page 3

    Signalling circuit frequency Minimum switching current Minimum switching voltage Non-overlap time Insulation resistance Environment IP degree of protection Protective treatment Pollution degree Ambient air temperature for operation Ambient air temperature for storage Permissible ambient air temperature around the de- vice ...