LC1D253M7 SQUARE D, LC1D253M7 Datasheet - Page 2

no-image

LC1D253M7

Manufacturer Part Number
LC1D253M7
Description
CONTACTOR 600VAC 25AMP IEC +OPTIONS
Manufacturer
SQUARE D
Datasheet
Complementary
Coil technology
Control circuit voltage limits
Inrush power in VA
Hold-in power consumption in VA
Heat dissipation
Auxiliary contacts type
Signalling circuit frequency
Minimum switching current
Minimum switching voltage
2
Associated fuse rating
Average impedance
[Ui] rated insulation
voltage
Electrical durability
Power dissipation per
pole
Safety cover
Mounting support
Standards
Product certifications
Connections - terminals
Operating time
Safety reliability level
Mechanical durability
Operating rate
Without built-in suppressor module
0.85...1.1 Uc at 60 °C operational 60 Hz
0.8...1.1 Uc at 60 °C operational 50 Hz
0.3...0.6 Uc at 60 °C drop-out 50/60 Hz
70 VA at 20 °C (cos ϕ 0.75) 50 Hz
70 VA at 20 °C (cos ϕ 0.75) 60 Hz
7 VA at 20 °C (cos ϕ 0.3) 50 Hz
7.5 VA at 20 °C (cos ϕ 0.3) 60 Hz
2...3 W at 50/60 Hz
Type mirror contact (1 NC) conforming to IEC 60947-4-1
Type mechanically linked (1 NO + 1 NC) conforming to IEC 60947-5-1
25...400 Hz
5 mA for signalling circuit
17 V for signalling circuit
40 A gG at <= 690 V coordination type 2 for power
circuit
63 A gG at <= 690 V coordination type 1 for power
circuit
10 A gG for signalling circuit conforming to IEC
60947-5-1
2 mOhm at 50 Hz - Ith 25 A for power circuit
600 V for signalling circuit certifications UL
600 V for signalling circuit certifications CSA
690 V for signalling circuit conforming to IEC
60947-1
600 V for power circuit certifications UL
600 V for power circuit certifications CSA
690 V for power circuit conforming to IEC 60947-4-1
1.4 Mcycles 40 A AC-1 at Ue <= 440 V
1.65 Mcycles 25 A AC-3 at Ue <= 440 V
1.25 W AC-3
3.2 W AC-1
With
Plate
Rail
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
CSA C22.2 n°14
BV
CCC
CSA
DNV
GL
GOST
RINA
UL
LROS
Power circuit: spring terminals 2 cable(s) 4 mm² -
cable stiffness: flexible - without cable end
Power circuit: spring terminals 1 cable(s) 4 mm² -
cable stiffness: flexible - without cable end
Control circuit: spring terminals 2 cable(s) 2.5 mm² -
cable stiffness: flexible - without cable end
Control circuit: spring terminals 1 cable(s) 2.5 mm² -
cable stiffness: flexible - without cable end
4...19 ms opening
12...22 ms closing
B10d = 20000000 cycles contactor with mechanical
load conforming to EN/ISO 13849-1
B10d = 1369863 cycles contactor with nominal load
conforming to EN/ISO 13849-1
15 Mcycles
3600 cyc/h at <= 60 °C

Related parts for LC1D253M7