LC2K09017F7 SQUARE D, LC2K09017F7 Datasheet - Page 2

no-image

LC2K09017F7

Manufacturer Part Number
LC2K09017F7
Description
REVERSING CONTACTOR 575VAC 9A IEC
Manufacturer
SQUARE D
Datasheet
Complementary
Environment
Control circuit voltage limits
Inrush power in VA
Hold-in power consumption in VA
Heat dissipation
Auxiliary contacts type
Signalling circuit frequency
Minimum switching current
Minimum switching voltage
Non overlap distance
Insulation resistance
IP degree of protection
Protective treatment
Ambient air temperature for operation
Ambient air temperature for storage
Operating altitude
Flame retardance
2
Associated fuse rating
Average impedance
[Ui] rated insulation
voltage
Electrical durability
Interlocking type
Mounting support
Standards
Product certifications
Connections - terminals
Operating time
Safety reliability level
Mechanical durability
Operating rate
0.2...0.75 Uc at <= 50 °C drop-out
0.8...1.15 Uc at <= 50 °C operational
30 VA at 20 °C
4.5 VA at 20 °C
1.3 W
Type instantaneous 1 NC
<= 400 Hz
5 mA for signalling circuit
17 V for signalling circuit
0.5 mm
> 10 MOhm for signalling circuit
IP2x conforming to VDE 0106
TC conforming to DIN 50016
TC conforming to IEC 60068
-25...50 °C
-50...80 °C
2000 m without derating derating in temperature
Requirement 2 conforming to NF F 16-102
Requirement 2 conforming to NF F 16-101
V1 conforming to UL 94
10 A gG for signalling circuit conforming to VDE
0660
10 A gG for signalling circuit conforming to IEC
60947
25 A aM for power circuit
25 A gG at <= 440 V for power circuit
3 mOhm at 50 Hz - Ith 20 A for power circuit
600 V for signalling circuit conforming to UL 508
690 V for signalling circuit conforming to IEC
60947-5-1
690 V for signalling circuit conforming to IEC
60947-4-1
690 V for power circuit conforming to IEC 60947-4-1
600 V for signalling circuit conforming to CSA 22-2
No 14
600 V for power circuit conforming to CSA 22-2 No
14
600 V for power circuit conforming to UL 508
1.3 Mcycles 9 A AC-3 at Ue <= 440 V
0.18 Mcycles 20 A AC-1 at Ue <= 440 V
Mechanical
Plate
Rail
BS 5424
IEC 60947
NF C 63-110
VDE 0660
CSA
UL
Faston connectors 1 6.35 mm
Faston connectors 2 2.8 mm
10...20 ms coil de-energisation and NO opening
10...20 ms coil energisation and NO closing
B10d = 20000000 cycles contactor with mechanical
load conforming to EN/ISO 13849-1
B10d = 1369863 cycles contactor with nominal load
conforming to EN/ISO 13849-1
5 Mcycles
3600 cyc/h

Related parts for LC2K09017F7