ATV32HU15M2 SQUARE D, ATV32HU15M2 Datasheet - Page 3

no-image

ATV32HU15M2

Manufacturer Part Number
ATV32HU15M2
Description
ATV32 2 HP 240V 1 PHASE
Manufacturer
SQUARE D
Datasheet
Environment
Communication port protocol
Type of connector
Physical interface
Transmission frame
Number of addresses
Method of access
Marking
Operating position
Width
Height
Depth
Product weight
Option card
Noise level
Electromagnetic compatibility
Standards
Product certifications
Pollution degree
IP degree of protection
Vibration resistance
Shock resistance
Relative humidity
Ambient air temperature for operation
Ambient air temperature for storage
Operating altitude
RoHS EUR status
RoHS EUR conformity date
CANopen
Modbus
1 RJ45 for Modbus/CANopen on front face
2-wire RS 485 for Modbus
RTU for Modbus
1...127 for CANopen
1...247 for Modbus
Slave for CANopen
CE
Vertical +/- 10 degree
60 mm
325 mm
245 mm
2.9 kg
Communication card CANopen daisy chain
Communication card CANopen open style
Communication card DeviceNet
Communication card Ethernet/IP
Communication card Profibus DP V1
43 dB conforming to 86/188/EEC
1.2/50 µs - 8/20 µs surge immunity test conforming to IEC 61000-4-5 level 3
Conducted radio-frequency immunity test conforming to IEC 61000-4-6 level 3
Electrical fast transient/burst immunity test conforming to IEC 61000-4-4 level 4
Electrostatic discharge immunity test conforming to IEC 61000-4-2 level 3
Radiated radio-frequency electromagnetic field immunity test conforming to IEC
61000-4-3 level 3
Voltage dips and interruptions immunity test conforming to IEC 61000-4-11
EN 55011 class A group 1
EN 61800-3 environments 1 category C2
EN 61800-3 environments 2 category C2
EN/IEC 61800-3
EN/IEC 61800-5-1
CSA
C-Tick
GOST
NOM 117
UL
2 conforming to EN/IEC 61800-5-1
IP20 conforming to EN/IEC 61800-5-1
1 gn (f = 13...200 Hz) conforming to EN/IEC 60068-2-6
1.5 mm peak to peak (f = 3...13 Hz) conforming to EN/IEC 60068-2-6
15 gn for 11 ms conforming to EN/IEC 60068-2-27
5...95 % without condensation conforming to IEC 60068-2-3
5...95 % without dripping water conforming to IEC 60068-2-3
-10...50 °C without derating
50...60 °C with derating factor
-25...70 °C
<= 1000 m without derating
1000...2000 m with current derating 1 % per 100 m
Compliant
1007
3