61F-GP-NH AC100 Omron, 61F-GP-NH AC100 Datasheet

no-image

61F-GP-NH AC100

Manufacturer Part Number
61F-GP-NH AC100
Description
LEVEL CONTROL
Manufacturer
Omron
Series
61Fr
Type
Level Control - High Sensitivityr
Datasheets

Specifications of 61F-GP-NH AC100

Applications
Supply and Drain Control
Mounting Type
Socket Mount (11 pos)
Voltage - Supply
100 VAC
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
61F-GP-NHAC100
61FGPNHAC100
Battery (24 VDC) allows use in locations
without AC power supply. AC sine-wave
voltage between electrodes enables stable
detection with no electric corrosion.
• Outputs can be set to self-hold at ON or OFF using special cir-
• Adjustable sensitivity, with an operating resistance range of 0 to
• Relay contact chattering conventionally caused by waves elimi-
• Meets CE marking and is a UL recognized component.
Features
The 61F can now run on DC power to allow energy savings, greater safety, and use in
emergency situations.
Ordering Information
Note: A variety of Holders are available to suit different types of application. For details, refer to 61F Floatless Level Controller
Combines DC Power
Supply with AC Sensing
Method
AC sine-wave signals are
sent to electrodes using a
built-in DC-AC converter,
preventing electric
corrosion and ensuring
safety.
Supports Multi-channel
Sensing
Power supply circuits and
detection circuits are
isolated, allowing more
than one Controller to be
used in the same tank.
Conductive Level Controller
Front Socket
Electrode Holder
cuits.
100 kΩ, allows use for a wide variety of liquids.
nated using open collector output, reducing contact wear.
Conductive Level Controller
61F-GPN-BT/-BC
(F030-E1-8).
Refer to Safety Precautions for Floatless Level
Controllers.
Product name
Lower limit
Mid-point
Upper limit
Oscillator
circuit
61F-GPN-BT 24VDC
Open collector (NPN)
PF113A-E
(See note.)
Detector
circuit
Control output
is possible for
upper limit,
mid-point, and
lower limit.
Open Collector Output
Signals can be used as
direct input for a PLC.
PNP output is also
possible using the
connection method.
Same Wiring for Supply
and Drainage
Supply control and
drainage control can be
performed with the same
wiring (short terminals 7
and 8 for supply control).
This makes it easy to
perform wiring and
confirm connection.
Model number
61F-GPN-BC 24VDC
Relay contact (SPST-NO)
Drainage
control
Chattering
CSM_61F-GPN-BT_BC_DS_E_3_1
Valve
Short-circuit
Supply
control
Pump
Load
1

Related parts for 61F-GP-NH AC100

61F-GP-NH AC100 Summary of contents

Page 1

... Open collector (NPN) Front Socket PF113A-E Electrode Holder (See note.) Note: A variety of Holders are available to suit different types of application. For details, refer to 61F Floatless Level Controller (F030-E1-8). Open Collector Output Signals can be used as direct input for a PLC. Detector PNP output is also ...

Page 2

... Life expectancy Accessories Wiring distance (See note 2.) Note: 1. The 61F may not operate at resistance settings close to zero. Adjust the sensitivity to match actual usage conditions. 2. The figure for wiring distance above is for when 600-V 3-core cabtire cable with a cross-sectional area of 0.75 mm ■ Characteristics Ambient operating temperature − ...

Page 3

... Also, to take signals for liquid level at several points, use terminal common for all of the Controllers and use terminal 5 of each Controller as an electrode. Note: If terminals 7 and 8 are shorted, operation of the 61F relay is “de-energizing” (i.e., energized normally and de-energized when liquid is present across the electrodes). Therefore, if the power supply connected across terminals 3 and 9 is interrupted, the output from terminals 10 and 11 will turn OFF, enabling detection of power interruptions ...

Page 4

... Do not connect the power supply in reverse. ALL DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527. In the interest of product improvement, specifications are subject to change without notice. 61F-GPN-BT/-BC Correct Use Mounting Mount to a panel of thickness mm. ...

Page 5

... Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments. WARRANTY OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified) from date of sale by OMRON. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS ...