Specifications of E2A3-S08KS03-M1-C1 OMC

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Wiring
High-tension Lines
Wiring through Metal Conduit:
If there is a power or high-tension line near the cable of the Proximity
Sensor, wire the cable through an independent metal conduit to pre-
vent against Proximity Sensor damage or malfunctioning.
Cable Extension
The standard cable length is less than 200 m.
The tractive force is 50 N.
Mounting
The Proximity Sensor must not be subjected to excessive shock with
a hammer when it is installed, otherwise the Proximity Sensor may
be damaged or lose its water-resistance.
Do not tighten the nut with excessive force. A washer must be used
with the nut.
<SUITABILITY FOR USE>
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of the products in the
customer’s application or use of the products.
Take all necessary steps to determine the suitability of the product for the systems, machines, and equipment with which it will be used.
<CHANGE IN SPECIFICATIONS>
Product specifications and accessories may be changed at any time based on improvements and other reasons. Consult with your OMRON
representative at any time to confirm actual specifications of purchased product.
10
M8
M12
M18
M30
Stainless Steel Model 9 N·m
Brass Model
Type
---
20 N·m
60 N·m
150 N·m
Torque
Maintenance and Inspection
Periodically perform the following checks to ensure stable operation
of the Proximity Sensor over a long period of time.
1. Check for mounting position, dislocation, looseness, or distortion
2. Check for loose wiring and connections, improper contacts, and
3. Check for attachment or accumulation of metal powder or dust.
4. Check for abnormal temperature conditions and other environ-
5. Check for proper lighting of indicators (for models with a set indi-
Never attempt to disassemble or repair the Sensor.
Environment
Water Resistivity
The Proximity Sensors are tested intensively on water resistance, but
to ensure maximum performance and life expectancy, avoid immer-
sion in water and provide protection from rain or snow.
Operating Environment
Store and operate the Proximity Sensor only within the given specifi-
cations.
Inrush Current
A load that has a large inrush current (e.g., a lamp or motor) will
damage the Proximity Sensor. Connect the load to the Proximity
Sensor through a relay.