EKI-1222-AE ADVANTECH, EKI-1222-AE Datasheet

Modbus

EKI-1222-AE

Manufacturer Part Number
EKI-1222-AE
Description
Modbus
Manufacturer
ADVANTECH
Datasheet

Specifications of EKI-1222-AE

No. Of Ports
2
Data Rate Max
921.6Kbps
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Introduction
The EKI-1200 series Modbus gateways are bi-directional gateways for integrating new and existing Modbus/RTU and Modbus/ASCII serial devices to newer TCP/IP networked-based
devices. The EKI-1221/1222/1224 feature two independent Ethernet ports and MAC addresses to provide a redundant networking mechanism to guarantee Ethernet networking
reliability. They provide a simple and cost-effective way to bring the advantage of remote management and data accessibility to thousand of devices that can not connect to a network.
The EKI-1221/1222/1224 provide a feature that can allow users to select master or slave operation mode for each serial port. They not only allow an Ethernet master to control serial
slaves, but also allow serial masters to control Ethernet slaves.
Specifications
Ethernet Communications
ƒ Compatibility
ƒ Speed
ƒ No. of Ports
ƒ Port Connector
ƒ Protection
Serial Communications
ƒ Port Type
ƒ No. of Ports
ƒ Port Connector
ƒ Data Bits
ƒ Stop Bits
ƒ Parity
ƒ Flow Control
ƒ Baud Rate
ƒ Serial Signals
ƒ Protection
Software
ƒ OS Support
ƒ Utility Software
ƒ Operation Modes
General
ƒ LED Indicators
ƒ Reboot Trigger
EKI-1221
EKI-1222
EKI-1224
EKI-1221
Serial Device Servers
IEEE 802.3, IEEE 802.3u
10/100 Mbps
2
8-pin RJ45
Built-in 1.5 KV magnetic isolation
RS-232/422/485, software selectable
EKI-1221: 1
EKI-1222: 2
EKI-1224: 4
DB9 male
7, 8
1, 2
None, Odd, Even, Space, Mark
XON/XOFF, RTS/CTS, DTR/DSR
50 bps ~ 921.6 kbps
RS-232: TxD, RxD, CTS, RTS, DTR, DSR, DCD, RI, GND
RS-422: TxD+, TxD-, RxD+, RxD-, GND
RS-485: Data+, Data-, GND
15 KV ESD for all signals
Windows 2000/XP/Vista
Advantech Serial Device Server Configuration Utility
Modbus RTU Master/Slave mode
Modbus ASCII Master/Slave mode
System: Power, System Status
LAN: Speed, Link/Active
Serial: Tx, Rx
Built-in WDT (watchdog timer)
EKI-1222
RoHS
COMPLIANT
2002/95/EC
EKI-1224
Mechanics
ƒ Dimensions (W x H x D) EKI-1221/1222: 37 x 140 x 95 mm
ƒ Enclosure
ƒ Mounting
ƒ Weight
Power Requirements
ƒ Power Input
ƒ Power Connector
ƒ Power Consumption
Environment
ƒ Operating Temperature -10 ~ 60° C (14 ~ 140° F)
ƒ Storage Temperature
ƒ Operating Humidity
Regulatory Approvals
ƒ EMC
ƒ Safety
ƒ Hazardous Location
Ordering Information
ƒ EKI-1221
ƒ EKI-1222
ƒ EKI-1224
Features
ƒ Provides 2 x 10/100 Mbps Ethernet ports for LAN redundancy
ƒ Integration of Modbus TCP and Modbus RTU/ASCII networks
ƒ Supports baud rates up to 921.6 kbps
ƒ Supports up to 16 connections and 32 requests simultaneously
ƒ Supports 31 slaves per serial port
ƒ Easy-managing Advantech Serial Device Server Configuration Utility for
ƒ Auto searching slave ID over configuration utility
ƒ Software selectable RS-232/422/485 communication
ƒ Mounts on DIN-rail, wall or panel
ƒ Built-in 15 KV ESD protection for all serial signals
ƒ Automatic RS-485 data flow control
Windows 2000/XP/Vista
EKI-1224: 55 x 140 x 95 mm
Metal with solid mounting hardware
DIN-rail, Panel
EKI-1221: 592g
EKI-1222: 600g
EKI-1224: 668g
12 ~ 48 V
Terminal block
EKI-1221: 2 W
EKI-1222: 2.5 W
EKI-1224: 4 W
-20 ~ 80° C (-4 ~ 176° F)
5 ~ 95% RH
CE, FCC Part 15 Subpart B (Class A)
UL (UL60950-1)
UL/cUL Class I, Division 2
1-port Modbus Gateway
2-port Modbus Gateway
4-port Modbus Gateway
1-port Modbus Gateway
2-port Modbus Gateway
4-port Modbus Gateway