DUR-110A Crouzet USA, DUR-110A Datasheet

VOLTAGE MONITORING RELAY, SPDT, 110VAC

DUR-110A

Manufacturer Part Number
DUR-110A
Description
VOLTAGE MONITORING RELAY, SPDT, 110VAC
Manufacturer
Crouzet USA
Series
URr
Datasheet

Specifications of DUR-110A

Contact Configuration
SPDT
Power Consumption
3.5VA
Supply Voltage Max
110VAC
Relay Mounting
DIN Rail
Control Voltage Type
AC
Relay Terminals
11 Pin Octal
Coil Voltage Vac Nom
110V
Rohs Compliant
No
Carry Current
10A
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
CONTROLS
5-26
UR SERIES
VOLTAGE CONTROL RELAY
UL listed
• AC or DC Voltage Control
• Manual or Automatic Operation
• Adjustable Threshold
• 5 to 50% Hysteresis Range
• LED Relay Status Indicator
1. AC/DC voltage control without latching:
2. AC/DC voltage control with latching:
SPECIFICATIONS:
Input . . . . . . . . . . . . . . . . . . . . . . . . 24 VDC, 24, 48, 110, 220 VAC
Power consumption
Hysteresis selection . . . . . . . . . . . 5 to 50% of set point
Repeat accuracy . . . . . . . . . . . . . . ±2% at a constant ambient
Output Relay . . . . . . . . . . . . . . . . . SPDT Relay
Contact material
Maximum loading
Maximum switching voltage . . . . . 250 VAC
Relay maximum power rating . . . . 2200 VA
Transient protection
Mechanical life of relay . . . . . . . . . 30 x 10
Electrical life of relay . . . . . . . . . . . 2 x 10
Repetition accuracy
Response time . . . . . . . . . . . . . . . . 100 ms on make
Operating temperature . . . . . . . . . -4°F to +140°F
Weight . . . . . . . . . . . . . . . . . . . . . . 7 oz. (200g)
Option: 24 VDC power – the voltage and the measured current must be
from separate sources.
ORDERING INFORMATION:
D = DIN-rail mounting
L = 11 pin plug-in
The output relay is energized when the voltage (AC peak voltage)
exceeds the selected threshold. It de-energizes when the voltage
falls below the hysteresis setting (5 to 50%) or when supply breaks.
The hysteresis is controlled by a potentiometer and its selection does
not change the chosen threshold.
The output relay is energized when the voltage reaches the selected
threshold and stays latched in this position. The contact between ter-
minal B1 and M (or 8 or 9) should be opened or the input power of
the device interrupted to reset.
0.1 to 10 V
0.4 to 40 V
4 to 400 V
AC or DC
MOUNTING
204 Airline Drive, Suite 300, Coppell, Texas 75019 / Tel: (800) 677-5311 / FAX: (800) 677-3865 / www.crouzet-usa.com
Control
Range
CSA recognized
. . . . . . . . . . . . . . AgCdO
Resistance
. . . . . . . . . . . . . 10 A AC resistive 8 A DC inductive
400 kΩ
10 kΩ
40 kΩ
. . . . . . . . . . . 24 VAC: 1 VA
Input
. . . . . . . . . . . 2500 volts
. . . . . . . . . . . ±0.5% at a constant ambient
±15%, 50/60 Hz
48 VAC: 1.2 VA
110 VAC: 3.5 VA
220 VAC: 7 VA
200 ms on break
Permanent
(max)
100 V
440 V
50 V
Acceptance load (input)
5
Products and specifications subject to change without notice.
6
at 2400 VA resistive load
operations
MOUNTING
Consult factory for application assistance.
D
-20°C to +60°C
10ms peak max.
Less than
100 V
300 V
750 V
250 VDC
30 W
SERIES
UR SP50
SERIES
UR
UR
WIRING DIAGRAM:
Threshold
Threshold
˜
+
˜
-
DUR
Latching
12 14
S1
R
S1
S2
R
A1 11
S2
S1
INPUT POWER
B1
E1
E2 E3
24A
M
A2
hysteresis
(+)0.1 to 10v
(+)0.4 to 40v
(+)4 to 400v
(-)0v
hysteresis
S1
3
4
2
5
CONTROLS
R
1
24A = 24VAC
24D = 24VDC
48A = 48VAC
110A = 110VAC
220A = 220VAC
6
INPUT POWER
LUR
1 1
7
10
8
9
Latching S2
(+)0.1 to 10v
(+)0.4 to 40v
(+)4 to 400v
(-)0v
Automatic
Unlatching
Manual
Unlatching

Related parts for DUR-110A

Related keywords