B84142A10R EPCOS Inc, B84142A10R Datasheet - Page 9

FILTER POWER LINE 10A 250V

B84142A10R

Manufacturer Part Number
B84142A10R
Description
FILTER POWER LINE 10A 250V
Manufacturer
EPCOS Inc
Datasheets

Specifications of B84142A10R

Filter Type
Power Line
Voltage - Rated
250V
Current
10A
Mounting Type
Chassis Mount
Termination Style
Stud Lug
Operating Frequency
50 to 60Hz
Current Rating (max)
10A
Voltage Rating Max
250VAC
Termination
Screw
Mounting Style
Flange
Product Length (mm)
70mm
Product Depth (mm)
70mm
Product Height (mm)
44.5mm
Voltage Rating
250 VAC / 250 VDC
Current Rating
10 A
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Inductance
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
B84142A 10R
B84142A0010R000
Important information
Please read all safety and warning notes carefully before installing the EMC filter and putting it into
operation (see
are not removed nor their legibility impaired by external influences.
Death, serious bodily injury and substantial material damage to equipment may occur if the appro­
priate safety measures are not carried out or the warnings in the text are not observed.
Using according to the terms
The EMC filters may be used only for their intended application within the specified values in low­
voltage networks in compliance with the instructions given in the data sheets and the data book.
The conditions at the place of application must comply with all specifications for the filter used.
EMC filters
Cautions and warnings
It shall be ensured that only qualified persons (electricity specialists) are engaged on work such
as planning, assembly, installation, operation, repair and maintenance. They must be provided
with the corresponding documentation.
Danger of electric shock. EMC filters contain components that store an electric charge. Danger­
ous voltages can continue to exist at the filter terminals for longer than five minutes even after
the power has been switched off.
The protective earth connections shall be the first to be made when the EMC filter is installed and
the last to be disconnected. Depending on the magnitude of the leakage currents, the particular
specifications for making the protective-earth connection must be observed.
Impermissible overloading of the EMC filter, such as impermissible voltages at higher frequen­
cies that may cause resonances etc. can lead to destruction of the filter housing.
EMC filters must be protected in the application against impermissible exceeding of the rated
currents by suitable overcurrent protective.
Warnings
). The same applies to the warning signs on the filter. Please ensure that the signs
9