B84299D1320B3 EPCOS Inc, B84299D1320B3 Datasheet

no-image

B84299D1320B3

Manufacturer Part Number
B84299D1320B3
Description
FILTER POWER LINE 32A 250V
Manufacturer
EPCOS Inc
Datasheet

Specifications of B84299D1320B3

Filter Type
Power Line
Voltage - Rated
250V
Current
32A
Mounting Type
Chassis Mount
Termination Style
Stud Lug
Operating Frequency
50 to 60Hz
Current Rating (max)
32A
Voltage Rating Max
250VAC/250VDC
Termination
Screw
Mounting Style
Flange
Voltage Rating
250 VAC
Current Rating
32 A
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Inductance
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Filter für:Netzleitungen
Two- and four-line filters
16 to 150 A
Multi-stage
Stopband attenuation up to 40 GHz
Features
Design
The electrical components are incorporated in an RF-tight case of stainless steel. The cables enter
through glands. The RF-tight termination of the openings is produced by specially shaped lids.
The conductors and equipment grounding conductor are connected by threaded bolts. The space
around the fixing holes is left as bare metal (unpainted) to ensure good RF contact with metal sur-
faces (chassis, ground).
Protective measures (grounding)
The high capacitances between the lines and ground require special protective measures. If there
are no product-specific requirements, protection with a secondary ground wire (diameter min.
10 mm
ing bolts at each end.
Resistors are incorporated in the filter to discharge capacitors after turn-off.
Installation
Filters are supplied complete with all parts required for RF-tight installation (fixing screws, flanges,
RF gaskets, cable glands) and installation instructions.
No welding is needed on the shielding wall, so any subsequent installation is quite simple. And the
uniform template of the attachment points allows straightforward replacement of a two-line filter by
a four-line filter for example.
Accessories and special versions
RF-tight flexible connector fittings in widths of 25 and 40 mm are available for installation spaced
away from the shielding wall.
Filters with an EMP protection add-on for surge currents up to 100 kA per line are available on
request.
To match requirements, filters can be supplied with different kinds of EMC or shielding cable glands.
Tests
All filters are 100% tested and the results are archived under a filter's serial number. If required, a
test report can be generated for the serial number.
Filters for Power Lines
16 to 150 A, 100 dB from 14 kHz
General-purpose use through design with separate lines without intercoupling
Use of single chokes
Insertion loss to CISPR 17
2
) in accordance with EN 50178 is necessary. For this purpose the filter case have connect-
22
12/01
B84299-+1***-B3
B84299-+1***-E3

Related parts for B84299D1320B3

B84299D1320B3 Summary of contents

Page 1

... Filters for Power Lines 16 to 150 A, 100 dB from 14 kHz Filter für:Netzleitungen Two- and four-line filters 16 to 150 A Multi-stage Stopband attenuation GHz Features General-purpose use through design with separate lines without intercoupling Use of single chokes Insertion loss to CISPR 17 Design The electrical components are incorporated in an RF-tight case of stainless steel. The cables enter through glands ...

Page 2

... Filters for Power Lines 16 to 150 A, 100 dB from 14 kHz Circuit diagrams Two-line filters B84299-+1***-B3 Circuit diagram 1 1 (16 … Circuit diagram 2 1 (100 A) 2 Four-line filters B84299-+1***-E3 Circuit diagram 3 1 (16 … Circuit diagram 4 1 (100 and 150 B84299-+1***-B3 B84299-+1***-E3 1‘ ...

Page 3

... Filters for Power Lines 16 to 150 A, 100 dB from 14 kHz Insertion loss (typical values Measurement circuit 50 Filter ~ ~ ~ [dB 120 dB e 100 SSB1693-7 12/01 B84299-+1***-B3 B84299-+1***-E3 SSB1698-D-E Measurement limit GHz ...

Page 4

... Filters for Power Lines 16 to 150 A, 100 dB from 14 kHz General technical data Rated voltage V R for two-line filters Rated voltage V R for four-line filters Rated current I R Max. admissible overcurrent I over Rated frequency f R Test voltages V T Voltage drop/phase V DC resistance R ...

Page 5

... A, 100 dB from 14 kHz Characteristics and ordering codes I Mecha max nical A version m Two-line filters < < < < < < 100 C < 3,5 2 100 D < 3,5 Four-line filters < < < < < < 100 C < 3,5 4 100 D < 3,5 4 150 C < 150 D < Dim. Circuit ...

Page 6

... Filters for Power Lines 16 to 150 A, 100 dB from 14 kHz Dimensional drawing 1 16-, 32- and 63-A filters Mechanical version C (cable glands at both ends) 155 – Fittings Cable gland with cutout sealing ring 63 RF-tight connection to shielding wall, see page 33. Shielded end 288 268 SSB1703-I-E ...

Page 7

... Filters for Power Lines 16 to 150 A, 100 dB from 14 kHz Dimensional drawing 2 16-, 32- and 63-A filters Mechanical version D (direct connection to shielding wall) 155 – Fittings Cable gland PG 29 with cutout 32 sealing ring 63 RF-tight connection to shielding wall, see page 33. Shielded end Connecting bolt M8 ...

Page 8

... Filters for Power Lines 16 to 150 A, 100 dB from 14 kHz Dimensional drawing 3 100-A filters Mechanical version C (cable glands at both ends) 155 Cable gland PG 42/PG 29 – Fittings R A 100 Cable gland PG 42 with cutout sealing ring RF-tight connection to shielding wall, see page 33. ...

Page 9

... Filters for Power Lines 16 to 150 A, 100 dB from 14 kHz Dimensional drawing 4 100-A filters Mechanical version D (direct connection to shielding wall) 155 – Fittings R A 100 Cable gland PG 42 with cutout sealing ring RF-tight connection to shielding wall, see page 33. Shielded end Connecting bolt M8 ...

Page 10

... Filters for Power Lines 16 to 150 A, 100 dB from 14 kHz Dimensional drawing 5 150-A filters Mechanical version C (cable glands at both ends) 155 –10 Connecting (at each end) I Fittings R 150 A Cable gland PG 42 with cutout sealing ring RF-tight connection to shielding wall, see page 33. bolt M10 ...

Page 11

... Filters for Power Lines 16 to 150 A, 100 dB from 14 kHz Dimensional drawing 6 150-A filters Mechanical version D (direct connection to shielding wall) 155 –10 Connecting bolt M10 (at each end) 288 268 10 I Fittings R 150 A Cable gland PG 42 with cutout sealing ring RF-tight connection to shielding wall, see page 33. ...

Page 12

... Filters for Power Lines 16 to 150 A, 100 dB from 14 kHz RF-tight connection to shielding wall with flexible connector fitting (mechanical version C) Shielded end I Flexible connector fitting R A (must be ordered separately) 16 … 63 Width 25 mm 100, 150 Width 40 mm RF-tight connection to shielding wall (mechanical version D) ...

Page 13

Herausgegeben von EPCOS AG Marketing Kommunikation, Postfach 80 17 09, 81617 München, DEUTSCHLAND  EPCOS AG 2002. Alle Rechte vorbehalten. Vervielfältigung, Veröffentlichung, Verbreitung und Verwertung dieser Broschüre und ihres Inhalts ohne ausdrückliche Genehmigung der EPCOS AG nicht gestattet. Mit den ...

Related keywords