Specifications of K8AB-TH11S AC/DC24

Input Type
RTD, Thermocouple (Multiple)
Controller Type
On/Off
Temperature Range
Selectable, Varies By Input Type
Output Type
Relay
Supply Voltage
24VAC/DC
Size
DIN Rail Module
Thermocouple Type
K, J, T, E
Operating Temperature Max
55°C
Operating Temperature Min
-10°C
Output Voltage Max
250VAC
Svhc
No SVHC (15-Dec-2010)
Accuracy
± 2%
Accuracy %
2%
Approval Bodies
CE,
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Features
-
Display Type
-
Communications
-
Lead Free Status / Rohs Status
 Details
Other names
K8AB-TH11S-AC24DC24
K8AB-TH11S-ACDC24
K8ABTH11SACDC24
Z2809
Compact and Slim Relay Ideal for
Temperature Alarms and Monitoring
• Excessive temperature increases can be prevented and
• Temperature monitoring in slim design with a width of just
• Simple function settings using DIP switch.
• Universal-input support for thermocouple or Pt100 sensor input.
• Selectable output relay: Non-fail safe/fail safe.
• Alarm status identification with LED indicator.
Features
• This Temperature Monitoring Relay was designed specially for
• A relay capacity of 3 A at 250 VAC (resistive load) is provided in a
• Settings can be made and functions can be selected using the DIP
• Reduce the number of models by using universal-input support for
Model Number Structure
■ Model Number Legend
1. Basic Model
2. Function
Ordering Information
■ List of Models
Note: 1. Refer to page 3 for setting ranges.
K8AB-TH1@@
K8AB-TH
22.5 × 90 × 100 mm
abnormal temperatures can be monitored.
22.5 mm.
monitoring abnormal temperatures to prevent excessive
temperature increase and to protect equipment.
slim body only 22.5 mm wide.
An output latch function is also supported.
switch.
thermocouple or Pt100 sensor input.
Temperature Monitoring Relay
K8AB-TH
K8AB: Measuring and Monitoring Relay
TH1: Temperature Monitoring Relay
1
2. Specify the power supply voltage when ordering. Different models must be ordered for 100 to 240 VAC and 24 VAC/DC.
Refer to Safety Precautions for All
Temperature Controllers.
Size
2
3
4
100 to 240 VAC Temperature
24 VAC/VDC
Supply voltage
input
Type
1 (relay)
Number of
outputs
Thermocouple/Pt100 Unit: 1°C/°F (0 to 399°C/°F)
Thermocouple
Thermocouple/Pt100 Unit: 1°C/°F (0 to 399°C/°F)
Thermocouple
Selecting Functions and Modes
• The following settings are provided: alarm mode (upper limit/lower
Terminal Wiring with Ferrules
• Wire with 2 × 2.5 mm
Third-party Certification of CE Mark Compliance, Certified UL
Standard Compliance, and Certified TÜV and SUD Standard
Compliance
3. Setting Range
4. Output Form
limit), enable/disable latch, °C/°F, relay output non-fail safe/fail safe,
setting protection.
1: Low-temperature range (0 to 399°C: setting in increments of
2: High-temperature range (0 to 1700°C max.: setting in
S: One SPDT relay output
Input type
1°C)
increments of 10°C)
Unit: 10°C/°F (See note 1.)
Unit: 10°C/°F (See note 1.)
Setting unit (setting range)
2
solid wire or 2 × 1.5 mm
CSM_K8AB-TH_DS_E_3_1
2
wiring ferrules.
K8AB-TH11S
K8AB-TH12S
K8AB-TH11S
K8AB-TH12S
Model
1

K8AB-TH11S AC/DC24 Summary of contents

Page 1

... Pt100 sensor input. Model Number Structure ■ Model Number Legend K8AB-TH1 Basic Model K8AB: Measuring and Monitoring Relay 2. Function TH1: Temperature Monitoring Relay Ordering Information ■ List of Models Size Supply voltage K8AB-TH 100 to 240 VAC Temperature 22.5 × 90 × 100 mm ...

Page 2

... Munsell 5Y8/1 (ivory) ABS resin (self-extinguishing resin) Mounted to DIN Track or with M4 screws 22.5 × 100 × × D × H) K8AB-TH 24 VAC 50/ VDC 2 W max. (24 VDC max. (24 VAC) 2 for 5 min with 10 sweeps each and Z directions 4 kV contact discharge (level 2) ...

Page 3

... Minimum setting increment E Pt100 399 399 Pt100 399 399 PLII 1,800 1,700 1,700 1,300 600 100 10° PLII 3,200 3,000 3,000 2,300 1,100 300 10°F K8AB-TH 3 ...

Page 4

... Input (current temperature) Alarm (red) indicator Non-fail safe, Alarm (relay) output Fail safe, Alarm (relay) output K8AB-TH Note: 1. The input power supply depends on the model: 100 to 240 VAC or 24 VAC/VDC (no polarity) 2. Wiring of the external input terminals is as shown below. Hysteresis width: 2°C ...

Page 5

... Temperature Monitoring Relay error. (See note 1.). Usage The output latch can be reset by pressing this button. (Enabled when latch is enabled.) (See note 2.) Set each digit of the alarm set temperature. K8AB-TH11S: x1, x10, x100 digits K8AB-TH12S: x10, x100, x1000 digits Default Upper-limit alarm OFF Lower-limit alarm Enabled ...

Page 6

... In the interest of product improvement, specifications are subject to change without notice. 100 ( (See note.) 1000 (500) (See note.) Note: Dimensions in parentheses are for the PFP-50N. K8AB-TH Mounting Hole Dimensions Two, M4 screws or two, 4-dia screws 5 102 90 5 Note: Pull out and use the hooks when mounting using screws. ±0.15 7.3 ±0.3 ± ...

Page 7

... Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments. WARRANTY OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified) from date of sale by OMRON. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS ...