09 47 474 7211 HARTING, 09 47 474 7211 Datasheet - Page 58

no-image

09 47 474 7211

Manufacturer Part Number
09 47 474 7211
Description
Ha-Vis Smart Patch Cable CAT.6 Yel. 10m
Manufacturer
HARTING
Datasheet

Specifications of 09 47 474 7211

Rohs Compliant
Yes
58
Han-Power
Features
• 6 IDC‘s + PE for 4.0 mm² to 6.0 mm² wires
• No interruption of the energy supply
• Space-saving and compact design
• Leading protective ground within the insert
• Assembly with standard tools
• 24 V power supply integrated
Assembly Details
Current carrying capacity
The Han-Power
serial power bus. Having assembled the energy supply
Han-Power
The cable mantle has to be removed, the conductor is placed
without interruption in the IDC.
Han-Power
manufactured acc. to DIN VDE 0281/ DIN EN 60 228 with wire
gauges of 4.0 mm² up to 6 mm². For the distribution of the
device Han-Compact
used. This power supply can be used with Han-Compact
The current carrying capacity of the connectors is limited by the
thermal load capability of the contact element material including
the connections and the insulating parts. The derating curve
is therefore valid for currents which flow constantly (non-inter-
mittent) through each contact element of the connector evenly,
without exceeding the allowed maximum temperature.
Measuring and testing techniques according to DIN EN 60 512-5
➀ Han
➁ Han
Secondary connection 2 x M12
®
®
Q 4/2 Wire gauge: 4 mm²
Q 4/2 Wire gauge: 6 mm²
®
®
S can be inserted at any place of the power cable.
S is suitable for cables with single strands
®
Ambient temperature
S connector is suitable for the assembly of
®
®
Han
with wire gauge 4 x 6 mm²
S with 1x Han
hoods or cable to cable housings are
®
Q 4/2 fully loaded
®
Q 4/2 with Power Supply 24 V
®
hood.
Specifications
Han-Power
Cables
Technical data power supply
Technical characteristics
Number of contacts
Electrical data
acc. to EN 61 984
Power side
Rated current
Rated voltage conductor - ground
Rated voltage conductor - conductor 690 V
Rated impulse voltage
Pollution degree
Signal side
Rated current
Rated voltage
Rated impulse voltage
Pollution degree
Rated voltage
acc. to UL/CSA
Insulation resistance
Material
Limiting temperatures
Flammability acc. to UL 94
Mechanical working life
Degree of protection acc. to DIN EN 60 529 IP 65
Design of conductor acc. to
Wire gauge
Wire gauge
Input data
Output data
Max. operating temperature
Efficiency
Reverse voltage
Tide overtime for power-fail
Low voltage system
Additionally features
Green LED marks normal operating condition.
- Power contacts
- Signal contacts
- mating cycles
- Number of single strands
- Outer diameter
- Number of single strands
- Outer diameter
®
S
DIN EN 61 984
DIN EN 60 664-1
4 + PE
2
40 A 400/690 V 6 kV 3
40 A
400 V
6 kV
3
10 A 250 V
10 A
250 V
4 kV
3
600 / 250 V
≥ 10
polycarbonate
-40 °C ... +125 °C
V 0
≥ 500
DIN VDE 0281
DIN EN 60 228
4 mm²
56 x 0.3 mm ∅
4.2 mm
6 mm²
84 x 0.3 mm ∅
4.8 mm
90 V ... 264 V AC
(50 Hz / 60Hz)
100 V … 300 V DC
24 V DC / 2 A
(adjustable from 23 V ... 29 V)
Pre-setting: 24.5 V ± 0,5 %
-20°C ... 85°C
>86% (at 230 V AC)
max 32 V
>20 ms
SELV / PELV
short-circuit proof
open-circuit proof
automatic switch off in
the case of short-circuit
10
4 kV