W68-X2Q110-10 TE Connectivity, W68-X2Q110-10 Datasheet

no-image

W68-X2Q110-10

Manufacturer Part Number
W68-X2Q110-10
Description
CIRCUIT BREAKER, HYD-MAG, 2P, 277V, 10A
Manufacturer
TE Connectivity
Series
W6r
Datasheet

Specifications of W68-X2Q110-10

Input Voltage Vac
277V
No. Of Poles
2
Current Rating
10A
Interrupting Capacity
5kA
Dielectric Strength
1.5kV
Trip Time
100s
Trip Time Max
100sec
Trip Time Min
9sec
Rohs Compliant
Yes
Dimensions are shown for
reference purposes only.
Agency Approvals
UL:
CSA: Certified as a Supplementary Protector. File LR15734.
VDE: Approved to VDE 0642/EN 60 934 (Circuit Breakers for Equipment)
Users should thoroughly review the technical data before selecting a product part
number. It is recommended that users also seek out the pertinent approvals files of
the agencies/laboratories and review them to ensure the product meets the
requirements for a given application.
Electrical Data
Auxiliary Switch: See Auxiliary Switch Ratings Table 2 for details.
Calibration: Breakers will hold 100% of rated current. Breakers may trip
Dielectric Strength: 50/60 or 400 Hz., 1500V: DC, 1100V.
Insulation Resistance: 100 Megohms at 500VDC.
Endurance: 10,000 on/off cycles - 6000 at rated load, 4000 at no load.
Approvals and Ratings Table 1
W6 Series
W9 Series
Features
• Designed for the international market. UL Recognized, CSA Certified,
• Ratings to 50 amps.
• Heavy duty #10-32 stud connections. (W9)
• Quick-connect or screw terminals. (W6)
• Optional 10 amp auxiliary switch.
• Several delay curve options.
• Trip-free operation.
Approvals and Ratings Table 2
UL/CSA
and VDE approved.
Maximum
Maximum
Voltage
277/480
Voltage
277/480
Number
Switch
277
250
250
277
277
250
250
250
65
65
Recognized as Supplementary Protector under UL 1077 . File
E69543.
License No. 73782.
A
between 101% and 124% of rated load (149% for 400 Hz.
units and 134% for AC/DC units). Breakers must trip at
125% of rated load and above (150% for 400 Hz. units and
135% for AC/DC units).
Units tested at six cycles per minute, 1 second on and 9
seconds off at 25°C ambient.
Frequency
Frequency
50/60
50/60
50/60
(Hz)
400
400
400
50/60
50/60
50/60 Hz.
DC
(Hz)
400
400
Voltage
DC
UL/CSA (All Circuit Functions)
UL/CSA (All Circuit Functions)
125
3Ø-Wye
3Ø-Wye
3Ø-Wye
3Ø-Wye
Phase
Phase
1
1
1
1
-
1
1
-
Current
(Amps)
10
Dimensions are in inches over
(millimeters) unless otherwise
specified.
Current
(Amps)
0.2 - 50
0.2 - 20
0.2 - 20
0.2 - 20
0.2 - 20
Current
Rating
21 - 50
21 - 50
(Amps)
0.2 - 50
0.2 - 50
0.2 - 20
0.2 - 50
0.2 - 50
Rating
.093 x .020 x .250
(2.36 x .51 x 6.40)
Terminals
WxTxL
Interrupting
Interrupting
Capacity
(Amps)
Capacity
(Amps)
2,000
5,000
2,500
5,000
2,500
1,250
2,500
2,000
5,000
5,000
2,500
2,500
Catalog 1308242
Issued 3-03
W6 Series
W9 Series
Maximum
Specifications and availability
subject to change.
Mechanical/Environmental Data
Operating Temperature: -40°C to +85°C.
Humidity: Meets requirements of Mil-STD-202 method 103.
Shock: Tested per Mil-STD-202, method 213, test condition C
Vibration:Tested per Mil-STD-202, method 201, 10-55 Hz., 0.06" (1.52mm)
Fungus And Moisture Resistance: Special moisture resistant finish
Marking: W6 units have ON and OFF molded on the rocker of rocker
Mounting: Units are mounted with two #6-32 screws from the front of the
Weight: Approximately 2.5 ounces per pole.
Typical Resistance and Impedance
Tolerance: 0.1 - 4.99 ± 15%; 5 - 9.99 ± 20%; 10 - 15 ± 25%; 16 - 30 ± 50%.
Voltage
415/240
W6/W9
Magnetic Hydraulic
Circuit Breakers
Maximum
Voltage
415/240
250
250
65
250
250
65
Current
(Amps)
10.0
20.0
30.0
40.0
50.0
0.2
1.0
2.0
5.0
(100g @ 6 ms).
total excursion in 2 planes.
actuated units (rocker actuated VDE units have international
“1” and “0”). W9 units have ON and OFF molded into the area
at the base of the toggle. International “1” and “0” symbols are
marked on the toggle for both W6 and W9.
panel. Metric models for use with M3 x 0.5 screws are
available. To maintain published performance specifications,
units should not be mounted more than 90° from their normal
upright position.
Frequency
Frequency
50/60
50/60
50/60
50/60
50/60
50/60
(Hz)
(Hz)
DC
DC
VDE (Circuit Function X)
VDE (Circuit Function X)
Resistance
(Ohms)
series
90
1.2
0.28
0.04
0.013
0.004
0.0027
0.002
0.0015
DC
Phase
Phase
1
1
-
1
1
-
applied to all ferrous parts.
Plastic parts are made of inherently
fungus resistant material.
Impedance
50/60 Hz.
(Ohms)
90
1.2
0.28
0.04
0.013
0.005
0.004
0.002
0.0015
Current
(Amps)
Current
(Amps)
Rating
Rating
0.2-50
0.2-30
0.2-30
0.2-50
0.2-30
0.2-30
31-50
31-50
www.tycoelectronics.com
Technical support:
Refer to inside back cover.
Impedance
Interrupting
Interrupting
180
(Ohms)
400 Hz.
Capacity
Capacity
(Amps)
(Amps)
2.0
0.50
0.05
0.025
0.0065
0.004
0.003
0.0025
2,000
5,000
2,000
5,000
2,000
5,000
2,000
5,000
P&B
119

Related parts for W68-X2Q110-10

W68-X2Q110-10 Summary of contents

Page 1

... Hz. (Amps) A 125 10 Dimensions are shown for Dimensions are in inches over reference purposes only. (millimeters) unless otherwise specified. Catalog 1308242 Issued 3-03 W6/W9 Magnetic Hydraulic Circuit Breakers Typical Resistance and Impedance Current (Amps) 0.2 1.0 2.0 5.0 10.0 20.0 30.0 40.0 50.0 Tolerance: 0.1 - 4.99 ± ...

Page 2

Time vs. Current Trip Curves For W6 Series and W9 Series AC 50/60 Hz. DC & 50/60 Hz. 400 Hz. CURVE 0 NON-TIME DELAY 10,000 TRIP TIMES OVERLOAD @ 50/60 Hz. & 400 Hz. 1000 125% 100 ms ...

Page 3

... Specifications and availability subject to change 25.0 35.0 45.0 Consult factory for 30.0 40.0 50.0 other values. W68-X2Q12-5 W68-X2Q12-30 W69-X2Q12-15 W68-X2Q12-7 W68-X2Q13-15 W69-X2Q12-20 W68-X2Q12-10 W68-X2Q110-10 W69-X2Q12-25 W68-X2Q12-15 W68-X2Q110-20 W69-X2Q12-30 W68-X2Q12-20 W69-X2Q12-5 W69-X2Q110-20 W68-X2Q12-25 W69-X2Q12-10 W69-X2Q110- 91 35.0 50.0 40.0 Consult factory for other values 45.0 ...

Page 4

Outline Dimensions - Toggle Actuator Models W6 Series 1.640 .245 .235 (41.66) (6.22) (5.97) LINE 29° 1.530 (38.86) 30° OFF 2.040 .67 (51.82) (17 .02) W6 Series 1 Pole 2 Pole Ø .590 ...

Page 5

Outline Dimensions - Rocker Actuator Models W6 Series .805 1.640 (20.45) (41.66) .390 (9.91) .180 (4.57) LOAD D 1.530 1.30 (38.86) 1.660 (33.0) (42.16) A LINE .235 (5.97) 2.430 (61.72) Panel Mounting Cutout .750 .750 (19.05) (19.05) .205 .375 .750 ...

Page 6

Engineering Notes Dimensions are shown for 124 reference purposes only. Catalog 1308242 Issued 3-03 Dimensions are in inches over Specifications and availability (millimeters) unless otherwise subject to change. specified. P&B www.tycoelectronics.com Technical support: Refer to inside back cover. ...

Related keywords